Tjernlund COP2 Constant Operating Pressure Exhaust Control 8504208 User Manual

Page 8

Advertising
background image

7

ADJUSTING THE EXHAUST PRESSURE SET POINT

The pressure set point is adjusted by positioning dip switches 6 - 1 to match the desired setting listed on the Pressure Setpoint
Table below. The factory set point is 0.10” W.C. The dip switches are located on the Red block on the top of the COP2 circuit
board. A dip switch is ON when pulled OUT towards you. A dip switch is OFF when pushed IN away from you.

CAUTION: Disconnect electrical power to COP2 L1 & N prior to adjusting dip switch settings.

ACCELERATION SPEED SETTINGS

Dip Switches 7-8 are used to select drive response time. Slow (30 sec) = 7 ON, 8 OFF, Medium (20 sec) = 7 OFF, 8 ON, Fast (10
sec) = 7 ON, 8 ON,

The Fast (7 ON, 8 ON) acceleration is the factory default. Acceleration adjustment is typically not required unless set points of
greater than 0.30” W.C. are selected or if the vent run is a long length.

6

5

4

3

2

1

-0.05

IN

IN

OUT

OUT

OUT

OUT

-0.06

IN

OUT

IN

IN

IN

IN

-0.06

IN

OUT

IN

IN

IN

IN

-0.07

IN

OUT

IN

IN

IN

OUT

-0.08

IN

OUT

IN

IN

OUT

IN

-0.09

IN

OUT

IN

IN

OUT

OUT

-0.10

IN

OUT

IN

OUT

IN

IN

-0.11

IN

OUT

IN

OUT

IN

OUT

-0.12

IN

OUT

IN

OUT

OUT

IN

-0.13

IN

OUT

IN

OUT

OUT

OUT

-0.14

IN

OUT

OUT

IN

IN

IN

-0.15

IN

OUT

OUT

IN

IN

OUT

-0.16

IN

OUT

OUT

IN

OUT

IN

-0.17

IN

OUT

OUT

IN

OUT

OUT

-0.18

IN

OUT

OUT

OUT

IN

IN

-0.19

IN

OUT

OUT

OUT

IN

OUT

-0.20

IN

OUT

OUT

OUT

OUT

IN

-0.21

IN

OUT

OUT

OUT

OUT

OUT

-0.22

OUT

IN

IN

IN

IN

IN

-0.23

OUT

IN

IN

IN

IN

OUT

-0.24

OUT

IN

IN

IN

OUT

IN

-0.25

OUT

IN

IN

IN

OUT

OUT

-0.26

OUT

IN

IN

OUT

IN

IN

-0.27

OUT

IN

IN

OUT

IN

OUT

-0.28

OUT

IN

IN

OUT

OUT

IN

-0.29

OUT

IN

IN

OUT

OUT

OUT

-0.30

OUT

IN

OUT

IN

IN

IN

-0.31

OUT

IN

OUT

IN

IN

OUT

-0.32

OUT

IN

OUT

IN

OUT

IN

-0.33

OUT

IN

OUT

IN

OUT

OUT

-0.34

OUT

IN

OUT

OUT

IN

IN

-0.35

OUT

IN

OUT

OUT

IN

OUT

-0.36

OUT

IN

OUT

OUT

OUT

IN

-0.37

OUT

IN

OUT

OUT

OUT

OUT

-0.38

OUT

OUT

IN

IN

IN

IN

-0.39

OUT

OUT

IN

IN

IN

OUT

-0.40

OUT

OUT

IN

IN

OUT

IN

-0.41

OUT

OUT

IN

IN

OUT

OUT

-0.42

OUT

OUT

IN

OUT

IN

IN

-0.43

OUT

OUT

IN

OUT

IN

OUT

-0.44

OUT

OUT

IN

OUT

OUT

IN

-0.45

OUT

OUT

IN

OUT

OUT

OUT

-0.46

OUT

OUT

OUT

IN

IN

IN

-0.47

OUT

OUT

OUT

IN

IN

OUT

-0.48

OUT

OUT

OUT

IN

OUT

IN

-0.49

OUT

OUT

OUT

IN

OUT

OUT

-0.50

OUT

OUT

OUT

OUT

IN

IN

-0.51

OUT

OUT

OUT

OUT

IN

OUT

-0.52

OUT

OUT

OUT

OUT

OUT

IN

-0.53

OUT

OUT

OUT

OUT

OUT

OUT

Pressure Setpoint Table

Output

WC

DIP switch settings

DIP SWITCHES

OUT = ON (Towards You)

IN = OFF (Away from You)

8 7 6 5 4 3 2 1

6

1

Advertising