UC1 UNIVERSAL CONTROL, MAC1E OR MAC4E AND WHKE INTERLOCK KIT

CONNECTED WITH A MILLIVOLT APPLIANCE

XN

R

UNI

V

E

R

S

A

L CO
NT
RO
LLE

R

D/N 9183046-9

CALL

AS APPLIANCE INTERLOCK VOLTAGE.

RED JUMPER POSITION MUST BE THE SAME

XL

J1

J2

DRY

115V

24V

IMPORTANT:

JUMPER

GENERATED

5 VDC

LEGEND:

115 VAC

WHKE GAS

SAFETY CIRCUIT ACROSS P1 & P2 OF UC1 IS NOT UTILIZED

WITH HEATING EQUIPMENT AS SHOWN.

IN THIS APPLICATION. SPILL SWITCH MUST BE INTERLOCKED

MILLIVOLT

PRESSURE

SWITCH

JUNCTION ADAPTER

THERMOCOUPLE

950-0470 (JA1)

LINEAR LIMIT

SPILL SWITCH

GAS

VALVE

30 MILLIVOLT WATER HEATERS REQUIRE USE OF THE

(ECO) OF WATER HEATER. LINEAR LIMIT SPILL SWITCH,

ON 750 MILLIVOLT (POWER PILE) WATER HEATERS WIRE
LINEAR LIMIT SPILL SWITCH IN SERIES WITH HIGH LIMIT

950-0470 THERMOCOUPLE JUNCTION ADAPTER.

950-0470 JUNCTION ADAPTER AND GAS PRESSURE
SWITCH ARE INCLUDED WITH WHKE KIT.

DO NOT
SUPPLY

POWER.

POWER!

BOARD-

50/60 Hz

SUPPLY
115 VAC

ELECTRICAL BOX.

GROUND

CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN

IMPORTANT:

CONNECTIONS WITH UC1, MAC1E OR MAC4E

Each millivolt appliance interlocked with the UC1, MAC1E or MAC4E must have its own WHKE kit installed. The WHKE Gas Pressure
Switch actuates the Venter through the A - B Dry contacts. The Linear Limit switch disables the heater in the event of a venting malfunc-
tion. IMPORTANT: Each millivolt appliance interlocked with the UC1, MAC1E or MAC4E must have its own Linear Limit spill switch.

1. Wire WHKE Gas Pressure Switch across A and B terminals on UC1, MAC1E or MAC4E. Do not supply voltage to A and B terminals.

2. Wire WHKE Linear Limit in series with thermocouple junction adapter or high limit ECO of heater.

3. Make sure RED voltage jumper on UC1, MAC1E or MAC4E is in the DRY position.

4. If not previously completed, connect 115 VAC supply voltage to L & N terminals on UC1. Crimp Ground wire to grounding spade

terminal in UC1. Important: Installer must supply overload and disconnect protection.

5. If not previously completed, connect ground from UC1 whip to Venter ground. Connect Black and White leads from UC1 whip

to Venter motor leads. Connect Blue and Yellow leads from UC1 whip to Venter Fan Prover switch. Prover Leads are not polarity
sensitive. If using a Draft Inducer and only venting millivolt appliances the PS1505 Fan Proving Switch is not necessary, see below
for further information.

DRAFT INDUCERS WITH ONLY MILLIVOLT APPLIANCES (PS1505 FAN PROVER NOT REQUIRED)
When venting only millivolt gas control(s) with a draft inducer, the PS1505 fan prover is not necessary. It will, however, be necessary to
"jumper" the P1 and P2 terminals on the UC1 Universal Control. Remove the call jumper across J1 and J2 and place it across P1 and
P2 on the UC1. Deactivate the Prover Status Check circuit by pushing the #9 dip switch up, or to the "deactivated" position in the UC1
Universal Control. See “Prover Status Check Dip Switch Settings” in the Venter or UC1 instruction manual. The P1 & P2 proving switch
circuit of the UC1 cannot control the burner operation of a millivolt gas control. When using a WHKE millivolt interlock kit, the appliance
safety shutdown is accomplished by the Linear Limit spill switch which detects flue gas spillage. WARNING: The P1 & P2 proving
switch circuit must only be jumpered when venting strictly millivolt appliances where the safety is provided by the Linear Limit.

HS-SERIES POWER VENTERS WITH ONLY MILLIVOLT APPLIANCES (FAN PROVING SWITCH PROVIDED)
When venting only millivolt gas control(s) with an HS-Series power venter connect Fan Prover leads as outlined above in step 5. The fan
prover will not control the millivolt gas valve, but its inclusion is beneficial to proper sequencing of the UC1 control.

MULTIPLE APPLIANCE INTERLOCKS WITH A MILLIVOLT AND A 24 -115 VAC CONTROLLED APPLIANCE
When using a WHKE millivolt interlock kit the millivolt appliance safety shutdown is accomplished by the Linear Limit spill switch which
detects flue gas spillage. The P1 & P2 proving switch circuit of the UC1 Universal Control cannot control the burner operation of a milli-
volt gas control. When co-venting a 24-115 VAC gas control with a millivolt gas valve (i.e. furnace and water heater combo) the P1 &
P2 proving switch circuit only interlocks the 24-115 VAC gas control. The millivolt appliance safety shutdown is accomplished by the
Linear Limit spill switch which detects flue gas spillage. WARNING: Do not jumper the P1 & P2 proving switch circuit when
co-venting millivolt and 24 - 115 VAC gas valves.