SPECIFICATIONS

Motor: 115/1/60, 3300 RPM, 212 watts, 2.28 FLA

Fan Proving Switch: Non-adjustable set point of -.05" W.C.

High Limit: Manual reset, N/C contacts, open at 135oF + 10oF.

UC1 Universal Control: See UC1 Universal Control Board Features on page 4.

Pre-Purge: Options (0, 5, 20, 35 seconds); Post-Purge: Factory set at 2 minutes, Options (0, 30 seconds or 1, 2, 4, 8, 16 minutes).

See page 5 for Pre / Post-purge options.

GENERAL INFORMATION

These units have been factory tested and rated in accordance with AMCA standard 210, Test Code for Air Moving Devices.

Each SideShot is electrically factory line tested before shipment.

After opening carton, inspect thoroughly for hidden damage. Wheel should rotate freely. If any damage is found notify freight
carrier and your distributor immediately and file a concealed damage claim.

INSTALLATION RESTRICTIONS

1. The SideShot may not be installed on condensing appliances.

2. For Natural Gas, LP Gas and Oil Fired appliances only.

3. The SideShot may not be installed on an appliance with an automatic valve having a manual opener unless the manual

opener has been rendered inoperative or the automatic valve has been replaced with a valve not equipped with a manual
opener.

4. The SideShot may only be installed on appliances equipped with a draft hood, draft diverter or barometric draft control.

5. The SideShot shall not be installed where flue gas temperatures exceed 650oF at its inlet. Flue gas temperature verification:

A) On oil fuel, verify flue gas temperature at SS1 inlet is at or above 250oF (121oC) after 5 minutes of operation during

setup. See “Oil Draft Adjustment Procedure” on page 18, step 10.

AND

B) Measure temperature of flue gases at the inlet to the SideShot at time of installation. Temperature should be

measured after appliance and SideShot have operated for at least 15 minutes, allowing flue gas temperature to stabilize.

6. Vent runs of over 15 linear feet should use an approved, insulated vent connector to prevent problems related to sulfur condensation.

Improper installation, adjustment, alterations, service or maintenance can cause injury, property damage or death. Refer to this
manual. For assistance or additional information consult a qualified installer, service agency or the equipment supplier.

Do not exceed the recommended input range of the SideShot. Under no circumstances shall the minimum draft adjustment be
used for the larger input range of this product. Improper adjustment may result in the dispersion of flue products (carbon monox-
ide) into the building interior causing carbon monoxide poisoning or death.

If oil nozzle is changed or other equipment is added perform “Draft Adjustment Procedure” on page 17 again.

12 1/4"

16 1/2"

27 3/8"

A

B

C

15 1/8"

8"

D

13 3/4"

E

F

7 3/4"

G

14 3/4"

H

23 1/4"

I

Rough-In
8” Height
8 3/8” Width

FRONT VIEW

SIDE VIEW