PLENUM AND VENT HOOD CLEARANCE FROM COMBUSTIBLES

With an inlet flue gas temperature of 650oF or below, the SideShot has been Listed for the following clearances from combustible
materials:

VENT HOOD TERMINATION CLEARANCES

The SideShot has been ETL Listed according to the requirements of the National Fire Protection Association #31, #54 and #211
as follows, (See Diagram A).

• The exit terminals of mechanical draft systems shall not be less than 7 feet above grade when located adjacent to public walk

ways.

• A venting system shall terminate at least 3 feet above any forced air inlet located within 10 feet.

• The venting system shall terminate at least 4 feet below, 4 feet horizontally from or 1 foot above any door, window or gravity air

inlet into any building.

• The bottom of the vent terminal shall be located at least 12 inches above grade.

• The exit terminal shall be so arranged that the flue gases are not directed so as to jeopardize people, overheat combustible

structures or enter buildings.

• Not to be less than 10 feet from an adjacent building.

The SideShot is also Listed to terminate a minimum of 12” below, above or horizontally from a soffit, deck or adjacent sidewall.

If possible, do not terminate the SS1 on a wall that faces the direction of the prevailing winds. Backdrafts by severe winds
can cause oil odors to remain in the structure and/or interrupt heating equipment operation.

6

DIAGRAM A

IMPORTANT

Vent Hood and top of Plenum: Zero Clearance
Plenum front and sides: 1/2 inch
Plenum rear: 3 inches