Vintage Cellars Condensate Pump User Manual

Warning, Introduction, Electrical connections

Advertising
background image

3.

Mounting the pump: the tank has two slots provided to mount the unit.

The slots are located on the ends of the tank (Figure 5). The unit should

be mounted either on the side of the air conditioner unit or nearby wall.

Pump must be level and the inlet must be below the coil drain. Conduit

fittings are not compatible with the plastic pump housing.

4.

The pump should not be installed in a manner that will subject it to

splashing or spraying.

5.

This pump is not intended for use inside air plenums.

ELECTRICAL CONNECTIONS

1.

Shut off electrical power at fuse box before making any connections. All

wiring must comply with local codes.

2.

Line voltage: Connect power cord to line voltage specified on motor and

nameplate. Power cord must be connected to a constant source of power

(not a fan or other device that runs intermittently). If power cord does not

have a plug, wiring is as follows: green (or green/yellow)—ground. Black

(or brown)— line. White (or blue)—neutral.

3.

Safety switch: The

safety overflow switch

should be connected

to a class II low volt-

age circuit. To control

a thermostatic circuit

the COM and NO

connections from the

safety switch are to be

wired in series with

the low voltage ther-

mostat circuit to shut

down the heating/AC

circuit. The COM and

NC switch contacts

may be used to actuate a low voltage alarm circuit (connected in series)

if the heating/cooling system can not be disrupted. The safety switch

comes from the factory with leads connected to the COM and NO switch

terminals. Typical hook-up of “NC” circuits would be (Figures 2 & 3).

4.

If fused plug is used on 230V units, a 1.0 amp fuse is recommended.

PIPING

1.

Run flexible tubing or pipe from evaporator drain into one of the three

pump inlets. Be sure inlet piping is sloped downward to allow gravity

flow (Figure 4). Extend the inlet piping into the tank from 1 to 3 inches to

ensure that it will not interfere with proper float operation. Be sure that

the inlet piping is cut at an angle where it enters the tank.

WhisperKOOL

1738 E. Alpine Ave. Stockton, CA 95205

1(800) 343-9463

www.whisperkool.com

INTRODUCTION

The condensate pump kit is designed as an automatic condensate removal

pump for water dripping off an air conditioner evaporative coil. The pump is

controlled by a float/switch mechanism that turns the pump on when approxi-

mately 2-1/4” of water collects in the tank, and automatically switches off when

the tank drains to approximately 1-1/4”.

The pumps are carefully packaged, inspected and tested to insure safe

operation and delivery. When you receive your pump, examine it carefully to

determine that there are no broken or damaged parts that may have occurred

during shipment. If damage has occurred, make notation and notify Whis-

perKool. They will assist you in replacement or repair, if required.

READ INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE

OR SERVICE THE LITTLE GIANT PUMP. KNOW THE PUMP APPLICATION, LIMITA-

TIONS AND POTENTIAL HAZARDS. PROTECT YOURSELF AND OTHERS BY OB-

SERVING ALL SAFETY INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS

COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE! RETAIN

INSTRUCTIONS FOR FUTURE REFERENCE. INSTALLATION AND CONNECTIONS

ARE TO BE MADE BY A QUALIFIED PERSON.

SAFETY GUIDELINE

DO NOT USE TO PUMP FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASO-

LINE, FUEL OIL, KEROSENE, ETC. DO NOT USE IN EXPLOSIVE ATMOSPHERES.

PUMP SHOULD BE USED WITH LIQUIDS COMPATIBLE WITH PUMP COMPONENT

MATERIALS.

DO NOT HANDLE PUMP WITH WET HANDS OR WHEN STANDING ON A WET OR

DAMP SURFACE, OR IN WATER. THIS PUMP IS SUPPLIED WITH A GROUNDING

CONDUCTOR AND/OR GROUNDING TYPE ATTACHMENT PLUG. TO REDUCE THE

RISK OF ELECTRICAL SHOCK, BE CERTAIN THAT IT IS CONNECTED TO A PROP-

ERLY GROUNDED GROUNDING TYPE RECEPTACLE.

IN ANY INSTALLATIONS WHERE PROPERTY DAMAGE AND/OR PERSONAL

INJURY MIGHT RESULT FROM AN INOPERATIVE OR

LEAKING PUMP DUE TO POWER OUTAGES, DISCHARGE LINE

BLOCKAGE, OR ANY OTHER REASON, A BACKUP SYSTEM(S) AND/OR ALARM

SHOULD BE USED.

SUPPORT PUMP AND PIPING WHEN ASSEMBLING AND WHEN INSTALLED. FAIL-

URE TO DO SO MAY CAUSE PIPING TO BREAK, PUMP TO FAIL, MOTOR BEARING

FAILURES, ETC.

WARNING

!

!

WARNING

!

!

INSTALLATION

1.

Before installing pump,

allow air conditioner

to cycle several times,

collecting condensate in

a separate container to

help flush any residual

oils that may remain in

the system.

2.

Carefully unpack the

pump. Remove the

cardboard packing from

the motor cover air

slots. Carefully slide the

packing away from the

pump. This packing is

used to prevent switch

movement during ship-

ment (Figure 1).

Remove cardboard

insert.

Connect here to turn alarm on.

Connect here to turn thermostat off.

NOTE: All wiring to be done by qualified service

technician. Refer to local codes in your area.

Safety Switch

(Low Voltage ClassII)

Discharge Line Installation

Inverted “U” Trap

Slope down from highest point

Drop to bottom of pump

or below if possible

Advertising