Drain Line

Drain Line

To: Garden

Sink

Sewer

Potted Plant

Pump Mounted to Wall

Extreme is for Example Only

Cooling System

2.

The outlet piping

should be flexible

tubing secured with

a hose clamp (not

provided) or pipe (3/8

inch I.D. maximum

to prevent excessive

flow back to unit).

From condensate unit,

extend discharge pip-

ing straight up as high

as necessary. Do not

extend this line above

the head/GPH of

the particular model

being installed. From

this high point, slope

discharge line down

slightly to a point

above drain area; then

turn down and extend

to a point below or approximately level with the bottom of the conden-

sate unit. This will give a siphoning effect which will improve efficiency

of the condensate unit and will, in most cases, eliminate the need for a

check valve (Figure 5). If it is not possible to slope discharge line down,

make an inverted “U” trap directly above the pump at the highest point.

SERVICE INSTRUCTIONS

1.

Make certain that the unit is disconnected from the power source before

attempting to service or remove any component!

2.

Be sure the floats move freely. Clean as necessary (Figure 6).

3.

Clean the tank with warm water and mild soap.

4.

Check the inlet and outlet piping. Clean as necessary. Be sure there are no

kinks in the line that would inhibit flow.

TESTING

1.

Turn on power.

2.

Remove motor/tank cover assembly and hold level.

3.

Test motor switch by raising motor switch float with finger (Figure 6). Mo-

tor should turn on just before float contacts cover.

4.

Test safety switch by raising safety switch float with finger. Safety switch

should activate before float contacts cover.

5.

Replace motor/tank cover assembly on tank. This pump is suitable for

gas furnace condensate applications. Caution must be taken to ensure

acidity of condensate does not increase below the average pH of 3.4 (to

prevent localized pocket of acid that acts like a battery causing pitting) by

routinely cleaning or flushing tank with fresh water.

Safety switch float

Motor switch float

Check Value

Mounting Slots