Power Supply

Problem Solving

Troubleshooting

The following table provides corrective action for possible trouble
situations. If further assistance is required, please contact a Crestron
customer service representative.

DIN-PWS50 Troubleshooting

TROUBLE

POSSIBLE

CAUSE(S)

CORRECTIVE

ACTION

24VDC LED
does not
illuminate.

DIN-PWS50 is not
receiving power.

Verify the DIN-PWS50
is connected to an AC
power line.

Fuse is blown.

Replace fuse with
T3.15AH (5 x 20 mm,
250 V, 3.15 A, time
lag, ceramic
cartridge). Refer to
“Fuse Replacement”
on page 12.

Output is
short-circuited.

Disconnect all output
connectors. LED will
light if problem was a
short circuit on output.







Operations & Installation Guide – DOC. 6667A

DIN Rail Power Supply: DIN-PWS50