Caution, Flammable vapor sensor testing – Bradford White D-4-504S6FSX User Manual

Page 27

Advertising
background image

Page 27

Gas Control Assembly to the Thermal Well (cont’d)
Step 8.

To resume operation, follow the instructions located on the water heater

lighting instruction label. Or, use the lighting instructions located in the water heater
installation and operating manual.

Flammable Vapor Sensor Testing

Step 1.

Move the gas control power switch to the “OFF”

position.

Step 2.

Disconnect the flammable vapor sensor harness from

the gas control.
Step 3.

Using a multi-meter set to the ohms setting, measure

the resistance of the flammable vapor sensor and resettable
thermal switch. The resistance must be between 3,000 and 48,000
ohms. If the resistance is out of this range, verify that the
resettable thermal switch has not been tripped. If it hasn’t, replace
the thermal switch.

120 VAC Circuit Trace
Step 1.

Verify 120VAC and proper polarity are at the wall outlet.

Step 2.

With the water heater plugged in and the gas control power switch in the

“ON” position verify LED status.

Flammable Vapor Sensor Testing

CAUTION

Do not use standard multi-meter probes for this testing. Doing so will damage the con-
nector. Use special pin type electronic probes or small diameter wire pins inserted into
connector.

Gas control power

switch

Flammable vapor

sensor harness

27