Bradford White TG-199E-N User Manual

Page 38

Advertising
background image

38

Table 17.

Thermal Fuse / Overheat Switch.

Wire Color

Voltage

Resistance

Connector

No.

Pin

Nos.

Red-Red

11-13 VDC

Below 1 ohms

F6

H1

F6-

H12



Flame Rod:
Place one lead of your meter to the flame rod and the other to ground. With the unit running, you should
read between 5-150 VAC. Set your meter to µ amp scale and series your meter in line with the flame rod.
You should read 1 µ amp or greater for proper flame circuit. In the event of low flame circuit, remove the
flame rod and check for carbon or damage.

Heat Exchanger and Outgoing Water Temperature Thermistors:
Check all Thermistors by inserting meter leads into each end of the thermistor plug. Set your meter to the
20k scale and read resistance. Applying heat to the thermistor bulb should decrease the resistance.
Applying ice to the thermistor bulb should increase the resistance. See below for examples of typical
temperatures and resistance readings.

Example:

59ºF = 11.4-14kΩ 140ºF

=

2.2-2.7kΩ

86ºF = 6.4-7.8kΩ 221ºF

=

0.6-0.8kΩ

113º = 3.6-4.5kΩ

Table 18.

Outgoing Water Thermistor.

Wire Color

Voltage

Resistance

Connector

No.

Pin

Nos.

White-White n/a

See example

above

F5 3-4

Table 19.

Heat Exchanger Temperature Thermistor.

Wire Color

Voltage

Resistance

Connector

No.

Pin

Nos.

Pink-White n/a

See example

above

F4 3-11

Table 20.

Intake Air Thermistor (Indoor Model Only).

Wire Color

Voltage

Resistance

Connector

No.

Pin

Nos.

Orange-White n/a

See example

above

F3 3-12

Table 21.

Surge Protector.

Wire Color

Voltage

Resistance

Connector

No.

Pin

Nos.

Black-White 108-132

VAC

n/a

D2

1-3

Blue-Brown 108-132

VAC

n/a

D1

1-3



With the power off, you can check the continuity through the surge protector. Place a meter lead on the
top pin #1 of the surge protector and pin #3 on the bottom of the surge protector. Check across the top
pin #3 and the bottom pin #1. If you read continuity across these two points, the surge protector is good.
If you do not get continuity, replace the surge protector.

Table 22.

Remote Controls.

Wire Color

Voltage

Resistance

Connector

No.

Pin

Nos.

Terminals B1

10-13 VDC

1.5-3.0k ohms

B

1-3