Installation – Vermont Casting Non-Catalytic Convection Heater 2477CE User Manual

Page 4

Advertising
background image

4

Dutchwest Non-Catalytic Convection Heater

30003849

Installation

SAFETY NOTICE: IF YOUR DUTCHWEST CON-
VECTION HEATER IS NOT PROPERLY INSTALLED,
OPERATED AND MAINTAINED, A HOUSE FIRE MAY
RESULT. FOR SAFETY, FOLLOW ALL INSTALLA-
TION, OPERATION AND MAINTENANCE DIREC-
TIONS. CONTACT LOCAL BUILDING OFFICIALS
ABOUT RESTRICTIONS AND INSTALLATION
INSPECTION REQUIREMENTS IN YOUR AREA.
Before you begin the installation, review your plans to
confirm that:
• Your stove and chimney connector will be far enough

from combustible material to meet all clearance
requirements.

• The floor protector is large enough and is construct-

ed properly to meet all requirements.

• You have obtained all necessary permits from local

authorities.

Your local building official is the final authority for ap-
proving your installation as safe and for determining
that it meets local and state codes.
The metal label permanently attached to the back of
every Dutchwest stove indicates the stove has been
tested to current standards. The test standard is
EN13240:2001 + A2:2004 for Europe. Clearance and
installation information is printed on the metal label at-
tached to the rear of the stove. Local authorities gen-
erally will accept the label as evidence that, when the
stove is installed according to the information on the
label and in this manual, the installation meets codes
and can be approved.
Codes vary in different areas. Before starting the instal-
lation, review your plans with the local building author-
ity. Your local dealer can provide any additional informa-
tion needed.
IMPORTANT: FAILURE TO FOLLOW THESE IN-
STALLATION INSTRUCTIONS MAY RESULT IN A
DANGEROUS SITUATION, INCLUDING A CHIMNEY
OR HOUSE FIRE. FOLLOW ALL INSTRUCTIONS
EXACTLY, AND DO NOT ALLOW MAKESHIFT COM-
PROMISES TO ENDANGER PROPERTY AND PER-
SONAL SAFETY.

All local regulations, including those referring to
national and European standards, need to be com-
plied with when installing this stove.

Chimney Types

Your Dutchwest Convection Heater must be connected
to a code-approved masonry chimney with a flue liner,
to a relined masonry chimney that meets local codes, or
to a prefabricated metal chimney.
Whatever kind you use, the chimney and chimney con-
nector must be in good condition and kept clean.

Masonry Chimneys

If you use an existing masonry chimney, it must be
inspected to ensure safe condition before the stove
is installed. Your local professional chimney sweep,
building inspector, or fire department official will be able
either to make the inspection or to direct you to some-
one who can.
An inspection of the chimney must confirm that it has
a lining. Do not use an unlined chimney. The chim-
ney should also be examined for cracks, loose mortar,
other signs of deterioration, and blockage. Repair any
defects before the chimney is used with your stove.

Unused openings in an existing masonry chimney must
be sealed with masonry to the thickness of the chimney
wall, and the chimney liner should be repaired. Open-
ings sealed with pie plates or wallpaper are a hazard
and should be sealed with mortar or refractory cement.
In the event of a chimney fire, flames and smoke may
be forced out of these unused thimbles.

The chimney should be thoroughly cleaned before use.

A newly-built masonry chimney must conform to the
standards of your local building code or, in the absence
of a local code, to a recognized national code. Masonry
chimneys must be lined, either with code-approved
masonry or pre-cast refractory tiles, stainless steel
pipe, or a code-approved, “poured-in-place” liner. The
chimney’s clean-out door must seal tightly.

The flue and chimney design must meet requirement
J2, Part J of the building regulations 2000 (Combustion
Appliances and Fuel Storage Systems).