HVAC Products

CC1B7865en

01.09.2005

19/57

5. Operating modes


In diagram area (1), the thermostat function is active.
In area (2), the controller maintains the adjusted setpoint.

A

B

q

A

q

(2)

(1)

W

HYS1

HYS3

X1

0%

100%

7865w05/1099


The positioning signal is delivered as a standard signal via the analog output.

)

The modulating controller must be available and configured in the unit (optional).

Ö

Section 8.2 «C112 limit comparator, controller type, setpoint «SP1», locking»



In diagram area (1), the thermostat function is active.
In area (2), a

2-position controller acts on the second stage, via relay 2 (open) and

relay 3 (close) by switching it into the circuit at the switch-on threshold «HYS1» / and out
of circuit at the switch-off threshold «HYS2».

q

A

B

q

A

I

II

(2)

(1)

W

HYS2

HYS1

HYS3

7865w06/1099


In area (3), the actual value exceeds the upper switch-off threshold «HYS3» and the
controller shuts down the burner (B). The controller only starts low-fire operation when
the level falls below the switch-on level «HYS1» again. If «Q» is exceeded, the controller
switches to high-fire operation (A).

Ö

Section 5.6 «Response threshold Q»


5.2.2 Modulating burner, analog output

5.2.3 2-stage burner, floating output