11. Technical data


For resistance thermometers, thermocouples or standard signals with 2

nd

order digital

filter (configurable).

In 2-wire or 3-wire circuit:

Type

Measured value range

Pt100, Pt1000, IEC 751

-200...+850 °C (-328...+1562 °F)

Ni100, Ni1000, DIN 43760

-60...+250 °C (-76...+482 °F)

LG-Ni1000

-50...+160 °C (-58...+320 °F)


Line resistance: < 30

Line compensation
Not required with 3-wire circuit.
When using a resistance thermometer in a 2-wire circuit, line compensation can only be
made by means of the offset correction.

Type

Measured value range

Fe-CuNi «J»

-200...+1000 °C (-328...+1832 °F)

NiCr-Ni «K»

-200...+1372 °C (-328...+2502 °F)

Cu-CuNi «T»

-200...+400 °C (-328...+752 °F)

NiCrSi-NiSi «N»

-100...+1300 °C (-148...+2372 °F)

Pt-RhPt «S»

0...1768 °C (-32...3214 °F) ¹)

Pt-RhPt «R»

0...1768 °C (-32...3214 °F) ¹)

Pt-RhPt «B»

0...1820 °C (32...3308 °F) ¹)


¹) Only with RWF40.0X2B97

Cold-junction temperature: Internal

Signal

Internal resistance Ri

Voltage drop

Ue

DC 0...10 V

R

i

= 2 M

DC 0...1 V

R

i

= 2 M

DC 0...20 mA

∆U

e

= < 1 V

DC 4...20 mA

∆U

e

= < 1 V


Sampling time: 210 ms


Resistance measured value 0…1 k

Ω standard signals without linearization.


With 2-wire circuit
R = 0…1 k



Signal

Internal resistance Ri

Voltage drop

Ue

DC 0...10 V

R

i

= 2 M

DC 0...20 mA

∆U

e

= 1 V

DC 4...20 mA

∆U

e

= 1 V


Sampling time: 630 ms

11.1 Inputs

11.1.1 Analog input 1 (actual value)

Resistance thermometers

Thermocouples

Standard signals

11.1.2 Analog input 2 (external setpoint, setpoint shift)

Potentiometer

Standard signals