During Annual Maintenance or More Frequent

Service Intervals, Verify the below items.

Note: The 7600 control has no serviceable internal

parts. DO NOT attempt to repair a malfunctioning

control.

□

The control is clean and all vents are free of dust, lint or

foreign material.

□

All wiring is tight, terminals are free from corrosion and

insulation is intact.

□

There is no physical damage to the case or display.

□

There is no evidence of water damage on the control or

terminals.

□

The control is securely mounted to the well or other

mounting support.

□

The sensor is in its place, with no evidence of tampering.

□

The sensor lead on remote mounted units is in good

condition and securely anchored in the immersion well

with the strain relief.

□

The control temperatures, differentials and optional

functions are set correctly and working to established

specifications. Consult the service tag or label on the

boiler.

□

A record of service and any adjustments are made to the

service label or tag.

□

The control door is attached and securely closed.

Before Leaving the Installation Site, Verify:

□

All wiring has been done correctly in a workmanlike way,

is secure and meets all applicable codes.

□

AquaSmart control temperature settings, differentials and

optional functions are correctly set.

□

The control program is functioning properly by observing

at least one complete cycle.

□

At shutdown, the temperature and pressure level match

the recommended settings.

□

The pressure relief valve operation and boiler water feed

system works properly by bleeding some water and

observing the refill cycle.

□

The low water cutoff operation by lowering the water level

until it shuts the burner off.

□

The boiler passages and vent system are clear of

obstructions and operating to the appliance

manufacturer’s specifications and all required clearance

dimensions to combustible materials are met.

□

With combustion test instruments the burner is set to

manufacturer’s specifications.

□

After the system has run through a complete cycle, that

all fittings are free of leaks.

□

A record has been made of all service work and all

temperature control settings and optional functions.

Attach a label or tag to the boiler for future reference.

□

The AquaSmart Installation Manual is left at a suitable

location near the boiler for future reference and the

equipment owner is informed of this.

□

The control door is attached and securely closed.

Service

Final Checklist

Accessories

7600RMU

AquaSmart Remote Mount Unit Pack

Includes:

○

Cable Assembly with Coupler

○

Mounting Template

○

Self-drilling Screws (Qty:3)

○

Cable Ty-wrap

7600TSU

AquaSmart Temperature Sensor Unit Pack

Includes:

○

Temperature Sensor

○

Cable Ty-wrap

○

Joint Compound

○

Installation Instructions

76002N1S01U

AquaSmart 2-in-1 Sensor Unit Pack

Includes:

○

2-in-1 Sensor

○

36” Ground Wire

○

Pipe Clamp for grounding

○

Installation Instructions

76002N1R03U

AquaSmart 2-in-1 Replaceable Sensor Unit Pack

Includes:

○

Thermowell

○

Sensor Probe

○

36” Ground Wire

○

Pipe Clamp for grounding

○

Installation Instructions