Instruction Manual MM850481 ed.01

SERIAL

Address :

0

Baud-rate

: 9600

ESCAPE

Use the [S] and [T] keys to move the cursor symbol to the desired option.

Press the [ENTER] key to set a new ID number or baud rate.

Press [ESCAPE] (F2) to return to the previous menu.

10.2.3 Analysis

Selecting this option you can change the analyzer auto-zeroing time and CH

4

& Natural gas heating probe time (we

suggest to use the pre-set values of 180 sec for autozero time and 60 sec for CH

4

heating time).

ANALYSIS

AutoZ. Time : 180

CH4 Heat. Time: 60

ESCAPE


Use the [S] and [T] keys to move the cursor symbol to the desired option.

Press the [ENTER] key to set a new Auto-zero time.

Press [ESCAPE] (F2) to return to the previous menu.

10.2.4

Leak test time

Selecting this option, you can change the timing for leak test using the decay method. The test has a total period of 310
seconds and the programmable time represent the interval between the measurements.

P DECAY TIME

Time P1 : 10

Time P2 : 60
Time P3 : 120

Time P4 : 120

ESCAPE

Use the [S] and [T] keys to move the cursor symbol to the desired interval.

Press the [ENTER] key to set new acquisition intervals.

Press [ESCAPE] (F2) to return to the previous menu.

45