Vent terminal clearances, U.s. installations, Page 4 – Louisville Tin and Stove DVCF408B-R User Manual

Page 4: Reference letter to drawing canadian installations

Advertising
background image

REFERENCE LETTER TO

DRAWING

CANADIAN INSTALLATIONS¹

U.S. INSTALLATIONS²

A = Clearance above grade, veranda,

porch, deck, or balcony

12 Inches (30 cm)

12 Inches (30 cm)

B = Clearance to window or door that

may be opened

12 Inches (30 cm)

DVCF40__ 9 Inches (23 cm)

DVCF55__ 12 Inches (30 cm)

DVCF65__ 12 Inches (30 cm)

C = Clearance to permanently closed

window

12 Inches (30 cm)

DVCF40__ 9 Inches (23 cm)

DVCF55__ 12 Inches (30 cm)

DVCF65__ 12 Inches (30 cm)

D = Vertical clearance to ventilated

soffit located above the terminal within

a horizontal distance of 2 Feet (61 cm)

from the center line of the terminal

18 Inches (46 cm)

18 Inches (46 cm)

E = Clearance to unventilated soffit

24 Inches (61 cm)

24 Inches (61 cm)

F = Clearance to outside corner

12 Inches (30 cm)

12 Inches (30 cm)

G = Clearance to inside corner

12 Inches (30 cm)

12 Inches (30 cm)

H = Clearance to each side of center

line extended above meter/ regulator

assembly

3 Feet (91 cm) within a height

15 Feet (4.5m) above the meter/regulator

assembly

Clearance in accordance with local

installation codes and the requirements

of the gas supplier

I = Clearance to service regulator vent

outlet

3 Feet (91 cm)

Clearance in accordance with

local installation codes and the

requirements of the gas supplier

J = Clearance to nonmechanical air

supply inlet to building or the

combustion air inlet to any other

appliance

12 Inches (30 cm)

DVCF40__ 9 Inches (23 cm)

DVCF55__ 12 Inches (30 cm)

DVCF65__ 12 Inches (30 cm)

K = Clearance to a mechanical air

supply inlet

6 Feet (1.83 m)

3 Feet (91 cm) above if within

10 Feet (3 m) horizontally

L = Clearance above paved sidewalk or

paved driveway located on public

property

7 Feet (2.13m) A vent shall not terminate

directly above a sidewalk or paved

driveway that is located between two

single family dwellings and serves both

dwellings.

Clearance in accordance with

local installation codes and the

requirements of the gas supplier.

M = Clearance under veranda, porch,

deck, or balcony

12 Inches (30 cm) permitted only if

veranda, porch, deck, or balcony is fully

open on a minimum of two sides.

Clearance in accordance with

local installation codes and the

requirements of the gas supplier.

¹ In accordance with the current CSA-B149.1 Natural Gas and Propane Installation Code
² In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code

Vent Terminal

Air Supply Inlet

Area where terminal is not permitted

VENT TERMINAL CLEARANCES

Page 4