Windy Nation Xantrex Complete Charge Controller User Manual

Page 6

Advertising
background image

6  

 

 

1.  Connect  your  DC  current  source  (PV,  wind,  hydro,  etc.)  directly  to  the  RE  disconnect.  

This  is  the  red  

wire  marked  “1”  in  Figure  3  below.  

 

2.  Connect  another  cable  from  the  other  side  of  the  RE  disconnect  to  the  battery  positive  terminal.  
3.  Run  a  negative  wire  from  the  DC  current  source  (PV,  wind,  hydro,  etc.)  to  the  battery  negative  
terminal.  

This  is  the  black  wire  marked  “3”  in  Figure  3  below

.  

4.  Connect  a  cable  from  the  Xantrex  controller  terminal  marked  BAT  POS  to  the  battery  disconnect.  

This  

is  the  red  wire  marked  “4”  in  Figure  3  below.  

5.  

 

Connect  a  cable  from  the  battery  disconnect  to  the  positive  terminal  of  the  battery.  

6.    Connect  a  cable  from  the  negative  battery  terminal  to  one  of  the  terminals  marked  COMMON  
NEGATIVES  on  the  controller’s  circuit  board.  

This  is  the  black  wire  marked  “6”  in  Figure  3  below.  

7.  Connect  a  cable  from  the  controller’s  other  terminal  marked  COMMON  NEGATIVES  to  the  negative  
terminal  of  your  DC  diversion  load.  

This  is  the  black  wire  marked  “7”  in  Figure  3  below.  

8.  Connect  a  cable  from  the  controller’s  terminal  marked  PV+/LOAD+  to  the  positive  terminal  of  the  DC  
diversion  load.  

This  is  the  red  wire  marked  “8”  in  Figure  3  below

.  

 

 

 

Figure  3:  Labeled  wires  inside  the  Xantrex  Complete  Charge  Controller  

 
 

Trouble  Shooting  the  Xantrex  Complete  Charge  Controller  
 
 
Refer  to  pages  66-­‐67  of  the  Xantrex  C-­‐Series  Owner’s  Manual  for  trouble  shooting  solutions  to  common  
set-­‐up  and  operating  issues.  