Technical specifications, Installation – Inovonics FA416 User Manual

Page 5

Advertising
background image

© 1997 Inovonics Wireless Corporation LIT-FA416-INSTALL

5

02304e 23-Oct-02

Technical Specifications:

Dimensions (housing):

6.38" x 3.60" x 1.10"


Weight:

6.9

oz.

9 oz FA416R and FA416DR


Environmental:

Operating

temperature:

32

°-140°F (0°-60°C)

Relative Humidity:

90% (non-condensing)


Electrical:

Power Requirement:

11 - 14 VDC, 450 mA

Power Consumption:

60 - 85 mA (without display)

75 - 225 mA (with display)

450 mA (with display and 5 relays active)

Typical:

60 mA (without display)

75 mA (with display)

115 mA (with display and 1 relay active)

Relay specifications:

1A @ 28VDC

0.5A @ 30VAC (resistive load)


Receiver:

Type:

frequency-hopping spread spectrum

Operating frequency:

902-928 MHz

Installation:

Power: Supply power and ground to terminals marked 13.6V and GND on the terminal block.


Mounting: Use supplied hardware to attach FA416 housing to wall or surface. Where possible, orient the

antenna side of the receiver toward the majority of transmitters on the site. This enhances reception.


Opening the housing: Insert a small flat screwdriver behind pry point indicator nubs on top or bottom of the

housing cover. Gently twist or pry the housing cover away from the base.


Installing the FA516 display: Always disconnect power from the FA416 receiver before installing or removing

the FA516 Display Module. Visually check the mating of pins and header to make sure that all pins are seated

in the header.

Note: If the FA516 display is purchased separately from the FA416, it will be packaged with a housing cover

and graphic panel to replace the original FA416 cover. (Specify housing type.)


Installing the case tamper: Connect leads from the Case Tamper terminal block to a zone on the hardwire

panel. The switch is N/C with the cover on.

Attention: The FA540 relay module is not compatible with the new FA416 and FA416D receivers. If

relay outputs are required, the receiver unit must be either the FA416R or the FA416DR . The FA541 single-

relay module can still be used to provide relay operation off of individual outputs.