Chapter 4 Checklist

4-2

4

English

ENGLISH

3. Check Using an Operation Test with the Machine Stopped

With the machine stopped, turn on the power of the SL-CHG and carry out the following tests using
the test piece included in the package. If the floating blanking function is active, do not use the at-
tached test piece, but use a proper test piece that conforms to the description given in the SL-R12EX
manual.

❏

The output status indicator (bar LED) on the SL-CHG turns red and stays red while the test piece is
present within the detection zone.

❏

When the power of the SL-CHG is turned on with no test piece in the detection zone, the output
status indicator as well as all eight bar LEDs turn green.

❏

The test piece can be detected regardless of its location as long as it is in the detection zone.

❏

If the SL-R11G restart interlock function is enabled, when the test piece is removed, confirm that
bar LEDs on the SL-CHG light up green, the output status indicator lights up red, and the SL-R11G
interlock indicator lights up yellow.

❏

When in the restart interlock state, the start/restart input causes the output status indicator to
change to green, and the SL-R11G interlock indicator to turn off.

❏

If the SL-R11G start interlock function is enabled, confirm that the bar LEDs light up green, the
output status indicator turns red, and the SL-R11G interlock indicator lights up yellow when the
power of the SL-CHG is turned on with no object in the detection zone.

❏

In addition, the output status indicator changes to green and the SL-R11G interlock indicator turns
off when there is a start/restart input while in the start interlock state.

Move the test piece for detection confirmation as illustrated in the figure below.

Star

t

Stop

4. Operation Test with the Machine Operating

This test confirms that the machine stops its operation.

❏

Place the test piece in the detection zone or protection zone of the SL-CHG. It is recommended to
try three locations: near the transmitter, near the receiver, and the central area of the detection
zone. The machine must stop by the detection of the test piece.

❏

The machine must remain stopped as long as the test piece is in the detection zone.

❏

The machine will not operate when the SL-CHG Series power supply has been interrupted.

❏

The overall response time of the machine, including the response time of the SL-CHG and the time
it takes for the machine to stop, must be shorter than the overall response time T used in the
calculation of safety distances (

See “2-2 Safety Distances” (

➮page 2-4)).