PRACTICAL GUIDE TO INSTALLATION

Properly insulate the area around the fan

to minimize building heat loss and gain.

(Fig.20)

Loose fill or batt insulation can be placed

directly over the fan housing in the attic.

Panasonic fans and fan/light combination

units do not create excessive heat that is
a common problem with recessed light

fixtures or some competitors' fan/light

combinations. Our efficient, cool-running
motors and our fluorescent lamp do not
create enough ambient heat to be subjected

to these limitations.

Four inch or six inch roof jack, wall cap,'

or soffit vent with backdraft damper

Mechanicaiiy connect duct to termination

and seal with mastic or approved foil
faced tape

2-3 ft straight run before eibow

in attic instailation,

cauik box to drywaii

Short piece of fiexibie duct heips
aiignment and absorbs sound.
Ciamps pius mastic or approved

foii faced tape at all flex joints

Foil tape tightly covers all metal

duct joints (glue PVC joints)

Fig.20

SPECIFICATIONS

Specifications

Model No.

Air

direction

Voltage

(V)

Frequency

(Hz)

Duct

diameter

(inches)

Noise

(sones)

Power consumption

(w)

Speed

(rpm)

Air volume

at 0.1 "WG

(CFM)

Weight

lb.(kg)

Fan

Lighting unit

Fluorescent lampNight lamp

FV-13VKML3
FV-13VKSL3
FV-13VKL3

Exhaust

120

60

6

0.8

16

32

4

746

130

11.7(5.3)

FV-08VKML3
FV-08VKSL3
FV-08VKL3

Exhaust

120

60

4

<0.3

8

32

4

869

80

11.2(5.1)

HVI Certified performance based on HVI Procedures 915,916,and 920.

■ Reference specifications

Model No.

Air

direction

Voltage

(V)

Frequency

(Hz)

Duct

diameter

(inches)

Noise

(sones)

Power

consumption

(W)

Speed

(rpm)

Air volume

at 0.1 "WG

(CFM)

Weight

Ib.(kg)

FV-13VKML3
FV-13VKSL3

Exhaust

120

60

6

0.6

11.2

708

110

11.7(5.3)

0.3

8

674

90

<0.3

6.3

661

70

<0.3

4.8

645

50

-

0.5 (*)

-

0

FV-08VKML3
FV-08VKSL3

Exhaust

120

60

4

<0.3

6.5

828

70

11.2(5.1)

<0.3

5.6

798

60

<0.3

4.8

776

50

<0.3

4.2

765

40

<0.3

3.8

756

30

-

0.5 (*)

-

0

Reference performance based on HVI Procedures 915, 915, and 920. [(*) Standby wattage.]

PRODUCT SERVICE____________________________________

Warning Concerning Removal of Covers.
The unit should be serviced by qualified technicians only.
Your product is designed and manufactured to ensure a minimum of maintenance.

Should your unit require service or parts, call Panasonic Call Center at 1-866-292-7292 (USA)
or 1-800-669-5165 (Canada).

Panasonic Corporation of North America

One Panasonic Way, Secaucus, New Jersey 07094

www.panasonic.com

Panasonic Canada Inc.

5770 Ambler Drive, Mississauga, Ontario L4W 2T3

T

1011-1

13

KML

3420

A

www.panasonic.ca

Printed in China

PDF created with pdfFactory Pro trial version www. pdffactory. com

Advertising
This manual is related to the following products: