Wiring for Damper Actuators and Control Valves

On/Off, 24V, 110/120/230V

Observe class 1 and class 2 wiring restrictions.

Transformer sizing = SY actuator draw X 1.25 (safety margin)
(Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
3.75A X 24 VAC = 90VA Transformer).

Indicates an action or condition that may cause irreversible damage to the
actuator(s) or associated equipment.

Equipment damage!
Power consumption and input impedance must be observed.

CAUTION

Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury. It may also be used to alert against unsafe practices.

Warnings and Cautions appear at appropriate sections throughout this
manual. Read these carefully.

Hazard Identification

INSTALLATION NOTES

24 VAC Transformer

Line
Volts

G Ground

1 Common

3 Open

4 Closed

5

6

7

HTR

A

B

C

D

E

F

LS3

A-C

(Open Indication)

LS4

D-F

(Closed Indication)

Contact Rating: 5A 250 VAC Max.

SY2…5-24

G Ground

1 Common

3 Open

4 Closed

5

6

7

HTR

A

B

C

D

E

F

LS3

A-C

(Open Indication)

LS4

D-F

(Closed Indication)

Contact Rating: 5A 250 VAC Max.

SY2…5-24

K1

Open

Close

K1-B

K1-A

Actuator A

Actuator B

G Ground

1 Common

3 Open

4 Closed

5

6

7

HTR

A

B

C

D

E

F

LS3

A-C

(Open Indication)

LS4

D-F

(Closed Indication)

Contact Rating: 5A 250 VAC Max.

G Ground

1 Common

3 Open

4 Closed

5

6

7

HTR

A

B

C

D

E

F

LS3

A-C

(Open Indication)

LS4

D-F

(Closed Indication)

Contact Rating: 5A 250 VAC Max.

SY2…12-110 (220)

SY2…12-110 (220)

Open

Close

K1-B

K1-A

Actuator A

Actuator B

120 and 230 VAC

N L1

H L2

NOTES

Caution: Power Supply Voltage.
• Isolation relays must be used in parallel connection of multiple actuators
using a common control signal input.
• "H" (L2) cannot be connected to terminal #3 and #4 simultaneously.
Required: Terminal #7 needs to be field wired to enable heater circuit.

SY1 -24

A

B

C

E

F

Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.

A-B (Open Indication)

LS4

LS3

A-E (Closed Indication)

SY1-110 (220)

A

B

C

E

F

Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.

A-B (Open Indication)

LS4

LS3

A-E (Closed Indication)

SY1 Contact Arrangements

G

G

G

K1

G

Actuators: SY1...5-24 SY1...12-110 SY1...12-220

0

7/10 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

Advertising
This manual is related to the following products: