AM Series Actuators, On/Off, Floating Point

Models

AMB24-3-X1

Technical Data

Power supply

24 VAC ± 20% 50/60 Hz
24 VDC ± 10%

Power consumption

running 2.0 W

holding 0.2 W

Transformer sizing

5.5 VA (class 2 power source)

Electrical connection

3 ft, 18 GA plenum rated cable
½” conduit connector

Overload protection

electronic throughout 0° to 95° rotation

Control

on/off, fl oating point

Input impedance

600

Ω

Angle of rotation

95°, adjustable with mechanical stop

Direction of rotation

reversible with protected

switch

Position indication

handle

Manual override

external push button

Running time

95 seconds

Humidity

5 to 95% RH non condensing (EN 60730-1)

Ambient temperature

-22°F to +122°F [-30°C to +50°C]

Storage temperature

-40°F to +176°F [-40°C to +80°C]

Housing

NEMA 2/IP54

Housing material

UL94-5VA

Agency listings†

cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1, CSA C22.2 No. 24-93,
CE according to 89/336/EEC
(and 2006/95/EC for line voltage and/or -S
versions)

Noise level

<45dB(A)

Quality standard

ISO 9001

Dimensions with 2-Way Valve

A

M_

G

M_LineRevise

d

Dimensions (Inches)

Non-Fail Safe

(psi)

Valve

Size

A

B

C

D(Max)

BHC

HD

HDU

F650HD(U)

2”

1.65

7.00

7.00

15.00

4.75

200

50

F665HD(U)

2½”

1.76

7.00

7.00

15.50

5.50

200

50

F680HDU

3”

1.78

7.00

7.00

16.00

6.00

50

D

B

C

A

BHC

Dimensions with 3-Way Valve

Dimensions (Inches)

Non-Fail Safe

(psi)

Valve

Size

A

B

C

D(Max)

BHC

HD

HDU

F750HD

2”

4.50

6.15

6.15

15.50

4.75

200

F765HDU

2½”

5.00

6.76

6.76

16.00

5.50

200

50

Sin

g

le_Butterfl

y

1

0

0

D

A

B

C

0

7/10 - Subject to change. © Belimo Air