INSTALLATION

23

NORTHVALE

, NJ

07647

INTERNATIONAL

, INC

.

APPD

.

DWN

.BY

SCALE

DATE

DATE

JK

NTS

121009

AERCO

SD

-A

-795

C

REV

.

AERCO MOTORIZED ISOLATION VALVE

4

BOILER CONTROL PANEL

WIRING DIAGRAM

NOTES

:

1.

MOTORIZED VALVES MUST BE SPRING RETURN OPEN

, POWER CLOSED

.

2.

MOTORIZED VALVES ELECTRICAL REQUIREMENTS

: 120

/1

/60

3.

CONTROL PANEL CONTACTS RATED FOR MAXIMUM OF

2

AMPS

.

4.

WIRE TO BE

16

AWG

.

5.

OPEN END SWITCH MUST CLOSE WHEN VALVE OPENS

. THIS WILL CLOSE THE

DELAYED INTERLOCK IN THE I

/O BOX AND ALLOW THE BOILER TO FIRE

.

6.

OPEN END SWITCH MUST OPEN WHEN VALVE CLOSES

. THIS WILL OPEN THE

DELAYED INTERLOCK AND PROHIBIT THE BOILER FROM FIRING

.

7.

THE AUX START ON DELAY MUST BE PROGRAMMED IN THE C

-MORE

. THE

DELAYED INTERLOCK MUST BE CLOSED BEFORE THIS TIME LAPSES

, OTHERWISE

,

THE BOILER WILL LOCKOUT AND GO TO A FAULT

.

AERCO MOTORIZED ISOLATION VALVE 4

BOILER CONTROL PANEL

L

N

120

VAC

, 60

Hz

, 1

PH

AERCO MOTORIZED ISOLATION

VALVE

4

BOILER CONTROL

PANEL CONTACT LABELS

5

1

6

2

7

3

8

4

17

9

13

18

10

14

19

11

15

20

12

16

MOTORIZED

VALVE

#1

DLY INT

OUT

24

V

____

AUX RELAY

NO

COM

NC

____NO

COM

FAULT RELAY

NC

____

COM

____IN

____

I/O BOX ON BOILER

#1

COMMON

CLOSE

OPEN END SWITCH

MOTORIZED

VALVE

#2

DLY INT

OUT

24

V

____

AUX RELAY

NO

COM

NC

____NO

COM

FAULT RELAY

NC

____

COM

____IN

____

I/O BOX ON BOILER

#2

COMMON

CLOSE

CLOSE

OPEN

NEUTRAL

BLR

#1

Relay

CLOSE

OPEN

NEUTRAL

CLOSE

OPEN

NEUTRAL

CLOSE

OPEN

NEUTRAL

BLR

#2

Relay

BLR

#3

Relay

BLR

#4

Relay

MOV

#1

MOV

#2

MOV

#3

MOV

#4

5

3

7

4

8

2

6

1

Boiler

#1

Relay

Boiler

#2

Relay

Boiler

#3

Relay

Boiler

#4

Relay

1

2

3

4

5

6

7

8

Close

9

13

Open

MOV

#1

17

"N

"

17

13

9

10

11

12

14

15

16

18

19

20

Close

10

14

Open

MOV

#2

18

"N

"

Close

11

15

Open

MOV

#3

19

"N

"

Close

12

16

Open

MOV

#4

20

"N

"

OPEN END SWITCH

Figure 10 - Basic Wiring Diagram Depicting Interfacing a BVC (4 Boiler Version) with Two Boilers