27. Press the ▲ arrow key until SET Valve

Position

appears on the C-MORE display.

28. Press the CHANGE key. SET Valve Position

will begin to flash.

29. Press the ▼ arrow key until the SET Valve

Position

reads 45% and press the ENTER

key.

30. Press the

down ▼ arrow key until CAL

Voltage 45%

is displayed.

31. Press the CHANGE key. CAL Voltage 45%

will begin to flash.

32. The oxygen level at the 45% valve position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

45% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

6.4 %

<100 ppm

<30 ppm

33. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.

34. Once the oxygen level is within the specified

range at 45%, press the ENTER key to store
the selected blower output voltage for the
45% valve position.

35. Press the ▲ arrow key until SET Valve

Position

appears on the C-MORE display.

36. Press the CHANGE key. SET Valve Position

will begin to flash.

37. Press the ▼ arrow key until the SET Valve

Position

reads 30%, then press the ENTER

key.

38. Press the

▼ arrow key until CAL Voltage

30%

is displayed.

39. Press the CHANGE key. CAL Voltage 30%

will begin to flash.

40. The oxygen level at the 30% valve position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

30% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

6.7 %

<100 ppm

<30 ppm


41. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.


42. Once the oxygen level is within the specified

range at 30%, press the ENTER key to store
the selected blower output voltage for the
30% valve position.

43. Press the ▲ arrow key until SET Valve

Position

appears on the C-MORE display.

44. Press the CHANGE key. SET Valve Position

will begin to flash.

45. Press the ▼ arrow key until the SET Valve

Position

reads 30%, then press the ENTER

key.

46. Press the

▼ arrow key until CAL Voltage

16%

is displayed.

47. Press the CHANGE key. CAL Voltage 16%

will begin to flash.

48. The oxygen level at the 16% valve position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

16% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

8.5 %

<100 ppm

<30 ppm

49. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.

50. Once the oxygen level is within the specified

range at 16%, press the ENTER key to store
the selected blower output voltage for the
16% valve position.