Installation – AERCO BMK 2.0 LN Natural Gas 2008 User Manual
Page 20
INSTALLATION
2-10
information concerning sealed combustion air). 
If the sealed combustion air option is not being 
used, an inlet screen will be attached at the air 
inlet on the top of the unit 
The more common methods of supplying 
combustion air are outlined below. For more 
information concerning combustion air, refer to 
the AERCO Benchmark Venting and Combus-
tion Air Guide, GF-2050. 
2.13.1 Combustion Air From Outside the 
Building 
Air supplied from outside the building must be 
provided through two permanent openings. Each 
opening must have a free area of not less than 
one square inch for each 4000 BTU/H boiler 
input. The free area must take into account 
restrictions such as louvers and bird screens. 
2.13.2 Combustion Air From Inside the 
Building 
When combustion air is provided from within the 
building, it must be supplied through two 
permanent openings in an interior wall. Each 
opening must have a free area of not less than 
one square inch per 1000 BTU/H of total boiler 
input. The free area must take into account any 
restrictions such as louvers. 
2.13.3 Sealed Combustion
The AERCO Benchmark 2.0LN Boiler is UL 
listed for 100%-sealed combustion. For sealed 
combustion installations, the screen on the air 
inlet duct of the unit must be removed. The inlet 
air ductwork must then be attached directly to 
the unit’s air inlet. 
In a sealed combustion air application, the 
combustion air ducting pressure losses must be 
taken into account when calculating the total 
maximum allowable venting run. See the 
AERCO Benchmark Venting and Combustion 
Air Guide, GF-2050. When using the boiler in a 
sealed combustion air configuration, each unit 
must have a minimum 8 inch diameter 
connection at the unit.