SAFETY DEVICE TESTING

Figure 6-4

SSOV Actuator Cover Location

6.10 PURGE SWITCH OPEN DURING
PURGE

The Purge Switch (and Ignition Switch) is
located on the Air/Fuel Valve. To check the
switch, proceed as follows:

1. Set the unit’s ON/OFF switch to the OFF

position. Place the unit in manual mode and
set the fire rate between 25% and 30%.

2. Remove the Air/Fuel Valve cover by rotating

the cover counterclockwise to unlock it and
then lift up (see Figure 6-5).

3. Remove one of the two wires (#171 or #172)

from the Purge Switch (Figure 6-6).

4. Initiate a unit start sequence.

5. The unit should begin it’s start sequence,

then shut down and display PRG SWITCH
OPEN DURING PURGE.

6. Replace the wire on the Purge Switch and

depress the CLEAR button. The unit should
restart.

6.11 IGNITION SWITCH OPEN DURING
IGNITION

The Ignition Switch (and the Purge Switch) is
located on the Air/Fuel Valve. To check the
switch, proceed as follows:

1. Set the unit’s ON/OFF switch to the OFF

position.

2. Place the unit in Manual Mode and set the

firing rate between 25% and 30%.

3. Remove the Air/Fuel Valve cover (Figure

6-5) by rotating the cover counterclockwise
to unlock and lift up to remove.

4. Remove one of the two wires (#169 or #170)

from the Ignition Switch (Figure 6-6).

5. Initiate a unit start sequence.

6. The unit should begin it’s start sequence

and then shut down and display IGN
SWITCH OPEN DURING IGNITION.

7. Replace the wire on the Ignition Switch and

press the CLEAR button. The unit should
restart.

Figure 6-5

Air/Fuel Valve Cover Location

6-5