CONTROL PANEL OPERATING PROCEDURES

3-10

8. With the unit firing properly, it will be

controlled by the temperature controller
circuitry. The boiler’s VALVE POSITION will
be continuously displayed on the front panel
bargraph.

25

TO

B

L

O

W

ER

AI

R

I

N

DIAL

(DETAIL “A”)

STEPPER

MOTOR

DETAIL “A”


Once the demand for heat has been satisfied,
the Control Box will turn off the dual SSOV gas
valves. The blower relay will be deactivated and
the Air/Fuel Valve will be closed. Standby will
be displayed.

3.10 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve
positions (% open) that start and stop the unit,
based on load. These levels are Factory preset
as follows:

Start Level: 20%

Stop Level: 18%

Figure 3-6.

Air/Fuel Valve In Ignition Position

Normally, these settings should not require
adjustment.

6. Up to 7 seconds will be allowed for ignition

to be detected. The igniter relay will be
turned off one second after flame is
detected.

Note that the energy input of the boiler is not
linearly related to the Air/Fuel Valve position
(% open). Refer to Table 3-7 for the relationship
between the energy input and valve open
position (%) for a unit running on Natural Gas.

7. After 2 seconds of continuous flame, Flame

Proven

will be displayed and the flame

strength will be indicated. After 5 seconds,
the current date and time will be displayed in
place of the flame strength.

Table 3-7

Relationship Between Air/Fuel Valve Position and Energy Input

Air/Fuel Valve

Position

(% Open)

Energy Input

(BTU/HR)

Boiler Energy Input

(% Of Full Capacity)

0 0 0

10 0

0

20 287,000 10%
30 486,000 16%
40 802,000 27%
50 1,180,000 39%
60 1,720,000 57%
70 2,300,000 77%
80 2,550,000 85%
90 2,720,000 91%

100 3,000,000 100%