Installation, Danger – AERCO BMK 3.0 LN Dual Fuel Jan 2011 User Manual

Page 18

Advertising
background image

INSTALLATION

2-8

mA OUT

RS-485
COMM.

+

-

+
-

ANALOG IN

SENSOR COMMON

OUTDOOR SENSOR IN

REMOTE INTL'K IN

B.M.S. (PWM) IN

SHIELD

+
-

+
-

(AIR) AUX SENSOR IN

NOT USED

EXHAUST SWITCH IN

DELAYED INTL'K IN

FAULT RELAY
120 VAC, 5A, RES

AUX RELAY
120 VAC, 5A, RES

G

RELAY CONTACTS:
120 VAC, 30 VDC
5 AMPS RESISTIVE

DANGER

120 VAC USED

IN THIS BOX

NOT USED

NOT USED

NC
COM
NO

NC
COM
NO

NOT USED

0 – 10V

AGND

Figure 2-11. I/O Box Terminal Strip

2.9.1 Constant Setpoint Mode

The Constant Setpoint Mode is used when it is
desired to have a fixed setpoint that does not
deviate. No wiring connections, other than AC
electrical power connections, are required for
this mode. However, if desired, fault monitoring
or enable/disable interlock wiring can be utilized
(see paragraphs 2.9.9.1 and 2.9.10).

2.9.2 Indoor/Outdoor Reset Mode

This mode of operation increases supply water
temperature, as outdoor temperatures decrease.
An outside air temperature sensor (AERCO Part
No. 122790) is required. The sensor MUST BE
wired to the I/O Box wiring terminals (see Figure
2-11). Refer to paragraph 2.10.1 for additional
information on outside air temperature sensor
installation.

2.9.3 Boiler Management System Mode

NOTE

BMS Model 168 can utilize either pulse
width modulation (PWM) or RS485
Modbus signaling to the Boiler. BMS II
Model 5R5-384 can utilize only RS485
signaling to the Boiler.

When using an AERCO Boiler Management
System (BMS), the field wiring is connected
between the BMS Panel and each Boiler’s I/O
Box terminal strip (Figure 2-11). Twisted
shielded pair wire from 18 to 22 AWG must be
utilized for the connections. The BMS Mode can
utilize either pulse width modulation (PWM)

signaling, or RS485 Modbus signaling. For PWM
signaling, connections are made from the
AERCO Boiler Management System to the
B.M.S. (PWM) IN terminals on the I/O Box
terminal strip. For RS485 Modus signaling,
connections are made from the BMS to the
RS485 COMM terminals on the I/O Box terminal
strip. Polarity must be maintained and the shield
must be connected only at the AERCO BMS.
The boiler end of the shield must be left floating.
For additional instructions, refer to Chapter 5,
paragraph 5.6 in this manual. Also, refer to GF-
108M (BMS Model 168) and GF-124 (BMS II
Model 5R5-384), BMS -Operations Guides.

2.9.4 Remote Setpoint and Direct Drive
Modes

The Benchmark 3.0 Dual-Fuel Boiler can accept
several types of signal formats from an Energy
Management System (EMS), Building
Automation System (BAS) or other source, to
control either the setpoint (Remote Setpoint
Mode) or air/fuel valve position - % open (Direct
Drive Mode) of the Boiler. These formats are:

• 4 to 20 mA/1 to 5 VDC
• 0 to 20 mA/0 to 5 VDC
• PWM – (Pulse Width Modulated signal. See

para. 2.10.4)

• Network (RS485 Modbus. See para. 2.10.7)

While it is possible to control a boiler or boilers
using one of the previously described modes of
operation, it may not be the method best suited
for the application. Prior to selecting one of
these modes of operation, it is recommended

Advertising