Section 7 - maintenance, 1 maintenance schedule, 2 spark igniter – AERCO KC1000 Low NOx Boiler equipped with C-More version 3.04 User Manual
Page 55: Warning, Table 1 maintenance schedule
MAINTENANCE
SECTION 7 - MAINTENANCE
7.1 MAINTENANCE SCHEDULE
The unit requires regular routine maintenance to 
keep up efficiency and reliability. For best 
operation and life of the unit, the routine 
maintenance procedures listed in Table 1 should 
be performed within the specified time periods. 
 
Appendix K contains recommended spare parts 
lists for maintenance of the KC1000 Boiler. 
Table 1 Maintenance Schedule
Para
Item
6
Mos.
12
Mos.
24
Mos.
Labor 
Time 
7.2 Spark
Igniter
(124570)
Inspect Replace
20 
mins. 
7.3 Flame
Detector
(G124837)
Inspect Replace
20 
mins. 
7.4 Combustion
Cal.
Check Check
1
hr.
7.5 Testing
of
Safety
Devices
Test
20 
mins. 
7.6 *Manifold
&
Tubes
Inspect
& clean
if
needed
4 hrs.
7.7 Water
Side
Inspection
Inspect
2
hr.
7.8 Condensate
Drain
Inspect
& clean
30
mins.
* Recommended only when unit will be run in an 
extreme condensing mode for prolonged periods 
of time. 
 
WARNING!
TO AVOID PERSONAL INJURY, BEFORE 
SERVICING: 
(A) DISCONNECT AC POWER FROM THE 
 UNIT. 
(B) SHUT OFF THE GAS SUPPLY TO THE 
 UNIT. 
(C) ALLOW THE UNIT TO COOL TO A SAFE 
 TEMPERATURE. 
 
7.2 SPARK IGNITER
The spark igniter assembly (124570) is located 
in the body of the burner (Figure 7.1). The igniter 
may be HOT. Care should be exercised. It is 
easier to remove the igniter from the unit after 
the unit has cooled to room temperature. 
 
To inspect or replace the Igniter (124570): 
 
1. Set
the
ON/OFF switch on the control panel
to the OFF position and disconnect AC 
power from the unit. 
2. To access the spark igniter, remove the
unit’s left side paneland left rear cover.
3. Disconnect the igniter cable from the igniter
contact.
4. Using a 15/16” open-end wrench, remove
the igniter from the burner shell.
5. Inspect the igniter for erosion or carbon
build-up. If there is substantial erosion of the 
spark gap or ground electrode, the igniter 
should be replaced. If carbon build-up is 
present, clean the igniter using fine emery 
cloth. Repeated carbon build-up on the 
igniter is an indication that a check of the 
combustion settings is required. See 
Section 
4 for Combustion Calibration
procedures.
6. Prior to reinstalling the igniter, a conductive
anti-seize compound must be applied to the 
igniter threads. 
7. Reinstall the igniter in the burner shell. Do
Not over-tighten. A slight snugging up is 
sufficient.
8. Reconnect the igniter cable.
9. Replace the left side panel and left rear
cover on the unit.
 
 
FLAME
DETECTOR
PROBE
LOWER
BURNER
SHELL
BURNER
HEAD
BURNER
PLATE
IGNITER
(124570)
FLAME DETECTOR
(124837)
STAGED
IGNITION
ORIFICE
Figure 7.1
Spark Igniter and Flame Detector Location
7-1