7. Loosen the 1/4” NPT union on the low NOx
staged ignition assembly (Figure 7.3).
8. Disconnect the staged ignition assembly 1/8”
elbow from the 3” long NPT nipple at the 
bottom of the burner shell. 
Figure 7.3
Burner Disassembly Diagram
 
9. Remove the 3” long NPT nipple and 1/4” 
O.D. tube (Figure 7.3) from the burner shell.
 
10. Using a 7/16” socket or open end wrench, 
remove the four 1/4-20 nuts on the gas inlet 
pipe flange at the burner. 
 
11. Using two 9/16” wrenches, remove the two 
3/8-16 hex nuts and bolts on the gas inlet 
pipe flange at the air/fuel valve (Figure 7.3). 
Remove the gas inlet pipe. 
 
12. Loosen the hose clamp on the air/fuel valve 
outlet (Figure 7.3).
 
13. Using a 1/2” socket wrench, remove the six 
5/16-18 hex nuts supporting the burner 
(Figure 7.3).
14. Lower the burner while sliding the air hose
off the air/fuel valve. Remove the burner 
through the rear of the unit. Due to space 
limitations, it will be necessary to separate 
the burner head and shell during the removal 
process. 
 
15. Disconnect the exhaust temperature sensor 
by unscrewing it from the exhaust manifold 
(Figure 7.4). 
Figure 7.4
Exhaust Sensor Connector Location
 
16. Disconnect the air/fuel valve 12-pin con-
nector from the KC wiring harness.
17. Disconnect wires #24 and #17 from the
blower proof switch (Figure 7.5).
 
 
Figure 7.5
Blower Proof Switch Wire Locations
18. Loosen the hose clamp on the air/fuel valve
inlet and slide the clamp back towards the 
blower (Figure 7.6). 
Figure 7.6
Air/Fuel Valve Inlet Hose Clamp
7-3