C-MORE CONTROL PANEL OPERATION
2.6 TUNING MENU
The Tuning Menu items in Table 2-4 are Factory
set for each individual unit. Do not change
these menu entries unless specifically requested
to do so by Factory-Trained personnel.
NOTE
The Breakpoint Menu items shown in the following
Table with an asterisk are displayed only if Unit
Type = Water Heater and the Heatr Bkpt Dsp
option in the Calibration Menu (Table 2-5) is
Enabled. These Breakpoint values correspond to a
130°F default setpoint
Table 2-4. Tuning Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Prop Band
1°F
120°F
70°F (Boiler)
8°F (Water Heater)
Integral Gain
0.00
2.00
1.00 (Boiler)
1.60 (Water Heater)
Derivative Time
(If Unit Type = Boiler)
0.00 min
2.00 min
0.00 min (Boiler)
0.10 min (Water Heater)
Min Load Adj
(If Unit Type = Water Heater)
-50°F 50°F
0°F
Max Load Adj
(If Unit Type = Water Heater)
-50°F 50°F
0°F
FFWD Temp
(If Unit Type = Water Heater)
30°F 245°F
Outlet Feedback
(If Unit Type = Water Heater)
On (Yes)
Off (No)
On (Yes)
Feedback Gain
(If Unit Type = Water Heater
& Heatr Tuning Dsp is
Enabled)
.01 1.00
0.05
Breakpt at 100%*
30°F
240°F
77°F
Breakpt at 90%*
30°F
240°F
81°F
Breakpt at 80%*
30°F
240°F
85°F
Breakpt at 70%*
30°F
240°F
91°F
Breakpt at 60%*
30°F
240°F
95F
Breakpt at 50%*
30°F
240°F
102F
Breakpt at 40%*
30°F
240°F
110°F
Breakpt at 30%*
30°F
240°F
112°F
Breakpt at 20%*
30°F
240°F
114°F
Breakpt at 10%*
30°F
240°F
130°F
Breakpt at 0%*
30°F
240°F
135°F
Reset Defaults?
Yes
No
Are You Sure?
No