Section 3 - control panel menu descriptions, 1 menu item descriptions, 2 factory defaults – AERCO C-More Controls User Manual

Page 17: C-more control panel operation

Advertising
background image

C-MORE CONTROL PANEL OPERATION


SECTION 3 -

CONTROL PANEL MENU DESCRIPTIONS

3.1 MENU ITEM DESCRIPTIONS

Descriptions of the menu items and options
contained in each of the six major menu
categories are listed and described in Table 3-1.
Factory Default values for each of these items
are summarized in Table 3-2.

3.2 FACTORY DEFAULTS

The factory default values for each menu item
are summarized in Table 3-2.

Table 3-1. Menu Item Descriptions

MENU LEVEL & OPTION

DESCRIPTION

OPERATING MENU

Active Setpoint

This is the setpoint temperature to which the control
is operating when operating in the Constant Setpoint,
Remote Setpoint or Outdoor Reset (Boiler Only)
Mode. When in the Constant Setpoint Mode, this
value is equal to the Internal Setpoint setting in the
Configuration Menu. When in the Remote Setpoint
Mode, this value is the setpoint equivalent to the
remote analog signal supplied to the unit. When
operating a Boiler in the Outdoor Reset Mode, this is
the derived value from the charts in Appendix C.

Aux Temp

For monitoring purposes only

Outdoor Temp

Displayed only if outdoor sensor is installed and
enabled.

Fire Rate In

Desired input fire rate. This would normally be the
same as the fire rate shown on the bar-graph (fire
rate out) when the boiler is operating.

Flame Strength

Displays flame strength from 0 to 100%.

Run Cycles

Displays the total number of run cycles from 0 to
999,999.

Run Hours

Displays total run time of unit in hours from 0 to
999,999.

Fault Log

Displays information on the last 10 faults (numbered
0 through 9).