General
environmental conditions

Operation

EN 60721-3-3

Transport

EN 60721-3-2

Storage

EN 60721-3-1

MX..461.., MX..461..P Climatic conditions

Class 3K5

Class 2K3

Class 1K3

Temperature

-5...+45 °C

-25...+70 °C

-5...+45 °C

Humidity

5...95 % r.h.

5...95 % r.h.

5...95 % r.h.

Mechanical conditions

EN 60721-3-6

Class 6M2

EN 60721-3-3

EN 60721-2

EN 60721-2

MX..461..P Mechanically active substances

Class 2M2

Class 2M2

Biological requirements

Class 3B2

Chemically active substances

Class 3C1

Mechanically active substances

Class 3M2

Connection terminals

System neutral

AC 24 V operating
voltage

System potential

Positioning signal

DC 0...10 V / 2...10 V / 4...20 mA

Measuring neutral (= G0)

Position feedback signal

DC 0...10 V

Force control input

R = Inner resistance between G0 and YM, approx 10 kΩ

Connection diagrams

If controller and valve receive their power from separate sources, only one
transformer may be earthed on the secondary side.
Common transformer

Separate transformer


Common transformer

U

Indication of valve position (only if required). DC 0 ...10 V → 0...100 % volumetric flow V

100

Twisted pairs. If the lines for AC 24 V power supply and the DC 0...10 V (DC 2...10 V,
DC 4... 20 mA) positioning signal are routed separately, the AC 24 V line need not be twisted.

Caution

Terminal assignment
for controller with
4-wire connection

(to be preferred!)

Terminal assignment