If the valve electronics prove faulty, the electronics module must be replaced by the
ASE1 (DN15…32) or ASE2 (DN40…65) replacement electronics module.
Mounting instructions no. 35678 are included.

Always disconnect power before fitting or removing the electronics module.

After replacing the electronics module, calibration must be triggered in order to
optimally match the electronics to the valve (refer to "Calibration", page 5).

Under operating conditions within the limits defined by the application data, the
actuator will become hot, but this does not represent a burn risk. Always
maintain the minimum clearance specified, refer to "Dimensions", page 12.

Disposal

Do not dispose of the actuator in domestic waste. This applies in particular to the PCB.
The law may demand special handling of certain components, or it may make
environmental sense.
Observer all current local laws.

Warranty

Observe all application-specific technical data.
If specified limits are not observed, Siemens Switzerland Ltd / HVAC Products
does not assume any responsibility.

Technical data

Functional actuator data

Power supply

Extra low-voltage only (SELV, PELV)

Operating voltage

AC 24 V +20 / –15 %

Frequency

45...65

Hz

Typical

power

consumption

P

med

Refer to table " Connection type ", page 7

Standby < 2 W (valve closed)

Rated apparent power S

NA

Refer to table " Connection type ", page 7

Required

fuse

I

N

Slow, refer to table "Wiring connection", page 7

Input

Positioning signal Y

DC 0/2...10 V or DC 4...20 mA

Impedance

DC 0/2...10 V 100 k

Ω // 5nF

DC 4...20 mA 100

Ω // 5nF

Forced control YF

Impedance

22

k

Ω

Close valve (YF connected to G0) < AC 1 V

Open valve (YF connected to G)

> AC 6 V

No function (YF not wired)

Positioning signal Y active

Output

Position feedback signal X

DC 0...10 V; load resistance > 500

Ω

Stroke

measurement

Nonlinearity

Inductive
± 3 % of end value

Positioning time

< 2 s

Electrical connection

Cable entry

2 x

∅ 20.5 mm (for M20)

Connection terminals

Screw terminals for 4 mm

2

wire

Minimal wire cross section

1.5 mm

2

Maximum cable length

Refer to "Connection type", page 7