TROUBLESHOOTING

7-9

KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued

FAULT INDICATION PROBABLE CAUSES

CORRECTIVE ACTION

SSOV FAULT

DURING PURGE

1. See SSOV SWITCH

OPEN

SSOV FAULT

DURING RUN

1. SSOV switch closed

for 15 seconds during

run.

1. Replace SSOV actuator.

SSOV RELAY

FAILURE

1. SSOV relay failed on

board.

1. Ensure that Neutral and Earth Ground are connected at

the source and there is no voltage measured between

them. Measurement should indicate near zero or no more

than a few millivolts.

2. Check the SSOV power wiring.
3. Press CLEAR button and restart unit. If fault persists,

replace Ignition/Stepper (IGST) Board.

SSOV

SWITCH OPEN

1. Actuator not allowing

for full closure of gas

valve

2. SSOV powered when

it should not be

3. Defective Switch or

Actuator

4. Incorrectly wired

switch.

1. Observe operation of the Safety Shut-Off Valve (SSOV)

through indicator on the Valve actuator and ensure that

the valve is fully and not partially closing.

2. If the SSOV never closes, it may be powered

continuously. Close the gas supply and remove power

from the unit. Refer fault to qualified service personnel.

3. Remove the electrical cover from the SSOV and check

switch continuity. If the switch does not show continuity

with the gas valve closed, either adjust or replace the

switch or actuator.

4. Ensure that the SSOV Proof of Closure switch is correctly

wired.

STEPPER MOTOR

FAILURE

1. Air/Fuel Valve out of

calibration.

2. Air/Fuel Valve

unplugged.

3. Loose wiring

connection to the

stepper motor.

4. Defective Air/Fuel

Valve stepper motor.

5. Defective Power

Supply Board or fuse

6. Defective IGST Board

1. Refer to GF-112 and perform Stepper Test (para. 6.3.5)

to ensure stepper motor rotates properly between the 0%

(fully closed) and 100% (fully open) positions. Verify that

the VALVE POSITION bargraph and the dial on the

Air/Fuel Valve track each other to indicate proper

operation. If operation is not correct, perform the Stepper

Feedback Calibration (GF-112, para. 6.2.1).

2. Check to ensure that the Air/Fuel Valve is connected to

the Control Box.

3. .Inspect for loose connections between the Air/Fuel Valve

motor and the wiring harness.

4. Replace stepper motor.

5. Check DS1 & DS2 LEDs on Power Supply Board. If they

are not steady ON, replace Power Supply Board.

6. Check “Heartbeat” LED DS1 and verify it is blinking ON &

OFF every second. If not, replace IGST Board.