APPENDIX D
D-1
WATER HEATER DEFAULT SETTINGS
MENU & OPTION
FACTORY DEFAULT
Setup Menu
Password
0
Language
English
Unit of Temp
Fahrenheit
Comm Address
0
Baud Rate
9600
Configuration Menu
Internal Setpt
130°F
Unit Type
KC Water Heater
Fuel Type
Natural Gas
Unit Size
1.0 MBTU
Heater Mode
Constant Setpoint
Remote Signal
(If Heater Mode = Remote Setpoint)
4 – 20 mA ,/ 1-5V
Outdoor Sensor
Disabled
Setpt Lo Limit
60°F
Setpt Hi Limit
200°F
Temp Hi Limit
210°F
Max Valve Position
100%
Aux Start On Dly
0 sec
Failsafe Mode
Shutdown
mA Output
Off
Lo Fire Timer
2 sec.
Setpt Limiting
Disabled
Setpt Limit Band
5°F
Network Timeout
30 seconds
HI DB Setpt En
30
Demand Offset
10
Deadband High
2
Deadband Low
2