to the RTU Open. Connect to the wires to the removable

Phoenix connectors and then reconnect the connectors to

the board.

Space Temperature (SPT) Sensors —
There are two types of SPT sensors available from Carrier,

resistive input non-communicating (T55, T56, and T59)

and Rnet communicating (SPS, SPPL, SPP, and SPPF)

sensors. Each type has a variety of options consisting of:

timed override button, set point adjustment, a LCD

screen, and communication tie in. Space temperature can

be also be written to from a building network or zoning

system. However, it is still recommended that return air

duct sensor be installed to allow stand-alone operation for

back-up. Refer to the configuration section for details on

controller configurations associated with space sensors.

S

33ZCT55SPT, space temperature sensor with override
button (T--55)

S

33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment (T--56)

S

33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and
setpoint adjustment (T--59)

Use 20 gauge wire to connect the sensor to the controller.

The wire is suitable for distances of up to 500 ft. (152 m).

Use a three--conductor shielded cable for the sensor and

setpoint

adjustment

connections.

If

the

setpoint

adjustment (slidebar) is not required, then an unshielded,

18 or 20 gauge, two--conductor, twisted pair cable may be

used.

Connect T--55: See Fig. 41 for typical T--55 internal

connections. Connect the T--55 SEN terminals to RTU

Open J20--1 and J20--2. See Fig. 60.

SEN

SEN

J20-1

J20-2

C08460

Fig. 60 -- RTU Open T--55 Sensor Connections

Connect T--56: See Fig. 43 for T--56 internal connections.

Install a jumper between SEN and SET terminals as

illustrated. Connect T--56 terminals to RTU Open J20--1,

J20--2 and J20--3 per Fig. 61.

SEN

J20-1

J20-2

SEN

SET

Jumper

J20-3

SET

C08461

Fig. 61 -- RTU Open T--56 Sensor Connections

Connect T--59: The T--59 space sensor requires a

separate, isolated power supply of 24 VAC. See Fig. 62

for internal connections at the T--59. Connect the SEN

terminal (BLU) to RTU Open J20--1. Connect the COM

terminal (BRN) to J20--2. Connect the SET terminal (STO

or BLK) to J20--3.

OR

SET

SEN

OPB

COM- PWR+

BLU (SPT)

BLK (STO)

24 VAC

SENSOR
WIRING

POWER
WIRING

BRN (COM)

NOTE: Must use a separate isolated transformer.

J20-3

J20-2

J20-1

C10291

Fig. 62 -- Space Temperature Sensor Typical Wiring

(33ZCT59SPT)

Indoor Air Quality (CO

2

) Sensor —

The indoor air quality sensor accessory monitors space

carbon dioxide (CO

2

) levels. This information is used to

monitor IAQ levels. Several types of sensors are available,

for wall mounting in the space or in return duct, with and

without LCD display, and in combination with space

temperature sensors. Sensors use infrared technology to

measure the levels of CO

2

present in the space air.

The CO

2

sensors are all factory set for a range of 0 to

2000 ppm and a linear mA output of 4 to 20. Refer to the

instructions supplied with the CO

2

sensor for electrical

requirements and terminal locations. See Fig. 46 for

typical CO

2

sensor wiring schematic.

To accurately monitor the quality of the air in the

conditioned air space, locate the sensor near a return--air

grille (if present) so it senses the concentration of CO

2

leaving the space. The sensor should be mounted in a

location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near

supply ducts, open windows, fans, or over heat sources.

Allow at least 3 ft (0.9 m) between the sensor and any

corner. Avoid mounting the sensor where it is influenced

by the supply air; the sensor gives inaccurate readings if

the supply air is blown directly onto the sensor or if the

supply air does not have a chance to mix with the room air

before it is drawn into the return airstream.

Wiring the Indoor Air Quality Sensor: For each sensor,

use two 2--conductor 18 AWG (American Wire Gage)

twisted--pair cables (unshielded) to connect the separate

48H