E Series CE/AGA Approved Intermittent Pilot Ignition Control Installation Instructions 5

Troubleshooting

If the system does not function properly, determine the
cause using the procedures in this section.
Before proceeding with troubleshooting the system, check
the following.

Preliminary Checks

‰

Are you using resistive wire between the module
spark (11) and the pilot connection?

‰

Are all mechanical and electrical connections tight?

‰

Is the system wired and grounded correctly?

‰

Is gas inlet pressure per manufacturer’s
specifications?

‰

Is the thermostat calling for heat?

‰

Is the system powered?

Table 1: LED Error Indications

LED Indications During Normal Operation
Orange once a second

Waiting Time (Prepurge)

Red rapid flashing

Safety Time Spark On (Trial for Ignition)

Steady green

Running Position Flame On (Run)

Orange once every 5 seconds

Inter-Waiting Time Between Cycles (Retry)

Orange once a second

Flame Loss Waiting Time (Inter-Purge)

LED Error Indications

Red Green

Error

1

0

Flame did not light in safety time (Trial for Ignition)

1

1

Flame sense circuit stuck on

1 2

Internal

fault

1

3

Line frequency or micro clock error

2

1

Pilot valve fault

2

2

Pilot valve relay contact fault

2

3

Main relay fault

2

4

Main valve relay contact fault

Note: More than 2 red blinks indicate micro-memory or software fault.