Figure 2: Typical G196 Gas Valve Installation and Wiring

Setup and Adjustments

Checkout

!

WARNING: Risk of Explosion or Fire.

Follow this or an equivalent checkout procedure
after installation. Before leaving the installation,
verify that the gas valve functions properly and that
the system has no gas leaks. Gas leaks can lead to
an explosion or fire, and may result in severe
personal injury or death.

Make sure all components are functioning properly by
performing the following test.

1.

Test all joints and connections for leaks with a

soap solution.

2.

Close the main upstream shutoff valve and wait

at least 5 minutes for unburned gas to escape
from the appliance, and then reopen the valves.

3.

Turn on the main electrical power switch and

close the thermostat contacts. The appliance
should operate in accordance with the
manufacturer’s specified sequence of operation.

4.

Turn the thermostat to a low dial setting to open

the contacts. All burner flames should be
extinguished. Repeat Steps 3 and 4 at least three
times.

5.

Return the thermostat to a normal setting before

leaving the installation.