Braeburn 5050 User Manual

Braeburn Equipment

Advertising
background image

MODEL

5050

USER MANUAL

Compatible with low voltage single stage gas,

oil or electric heating or cooling systems,

including single stage heat pumps. This

thermostat can also be used on 250mv to

750mv millivolt heating only systems. Do not

use this thermostat on applications with

voltages above 30 Volts AC.

READ ALL INSTRUCTIONS BEFORE PROCEEDING

© 2005 Braeburn Systems LLC • Patents Pending • All Rights Reserved. Pub. No. 5050-100-006

WARNING!

Important Safety Information

SPECIFICATIONS

1

1

1

• Electrical Rating: 24 Volt AC (18-30 Volt AC)

1 amp maximum load per terminal

2 amp total maximum load (all terminals)

• Control Range: 45˚ - 90˚ F (7˚ - 32˚ C)

• Accuracy: +/- 1˚ F (+/- .5˚ C)

• DC Power: 3.0 Volt DC (2 "AA" Alkaline batteries included)

• Compatibility: Compatible with low voltage single stage gas, oil or electric heating

or cooling systems, including single stage heat pumps. This thermostat can also

be used on 250mv to 750mv millivolt heating only systems.

• Terminations: Rc, Rh, G, W, Y, B, O

INSTALLATION

2

2.1

Replacing Existing Thermostat

1. Always turn off power to the air conditioning or heating system prior to removing

existing thermostat.
2. Remove the cover of your old thermostat and locate the wire terminals. Do not

remove wires from terminals yet.
3. Using small pieces of masking tape, label wires prior to removal from terminals. Use

the chart below to determine the new terminal designations for your new thermostat.

Old Terminal from

New Terminal for

Existing Thermostat New Thermostat Terminal Description
V or Rc

Rc

Cooling Transformer

M, 4, Rh, or R

Rh

Heating Transformer

G or F

G

Fan Control

H, W or 4

W

Heating Control

Y

Y

Cooling Control

B

B

Reversing Valve (Heating)

O

O

Reversing Valve (Cooling)

C

None (Cap the wire) 24 Volt AC, Transformer Common

Premier Series

Universal 7 Day or 5-2

Day Programmable

Single Stage Heat/Cool

Digital Thermostat

CONTENTS

SPECIFICATIONS
INSTALLATION
TESTING YOUR NEW THERMOSTAT
PROGRAMMING
ADDITIONAL OPERATION FEATURES
TROUBLESHOOTING
WIRING DIAGRAMS

1

2

3
4
5
6
7

• Always turn off power to the air conditioning or heating system prior to installing,

removing, cleaning or servicing thermostat.

• Read manual thoroughly prior to installing, programming or operating thermostat.

• This thermostat is designed for use with a 24 Volt-AC low voltage single stage

gas, oil or electric heating or cooling systems, including single stage heat

pumps. This thermostat can also be used on 250mv to 750mv millivolt heating

only systems.

• Do not use this thermostat on applications with voltages above 30 Volts AC.

• This thermostat requires two (2) properly installed "AA" alkaline batteries to

provide power for the thermostat to properly control the system operation.

• Wiring must conform to all building codes and ordinances as required by local and

national code authorities having jurisdiction.

• Do not short (or jumper) across terminals on the gas valve or at the heating or

cooling system control board to test the thermostat installation. This could

damage the thermostat and void the warranty.

• Do not select COOL mode of operation if the outside temperature is below 50˚ F

(10˚ C). This could damage the controlled cooling system and cause personal injury.

• This thermostat should only be used as described in this manual. Any other use is

not recommended and will void the warranty.