Conventional systems – Braeburn 2220 User Manual

Page 5

Advertising
background image

4

1 HEAT / 1 COOL Single or Dual Transformer

Set Installer Switch to CONV

Rh 24 Volt AC Power (heating transformer) [note 2]
Rc
24 Volt AC Power (cooling transformer) [note 2]
W1
Heat Relay (appears as W1/E on 2220)
Y1 Compressor Relay
G Fan Relay
C 24 Volt AC Transformer Common [note 1, 3]

Typical Wiring Configurations

NOTE: The “Installer Switch” option will be configured in the next step.

Conventional Systems

24VAC Power
Terminal (C)

NOTES - Conventional Systems

[1] If batteries are installed the 24 Volt AC common connection is optional
[2] Remove factory installed jumper for dual transformer systems
[3] In dual transformer systems, transformer common must come from

cooling transformer

[4] If needed for system

Provide disconnect and overload protection as required.

2 HEAT / 2 COOL Single or Dual Transformer (2220 Only)

Set System Type to CONV

Rh

24 Volt AC Power (heating transformer)

[note 2]

Rc

24 Volt AC Power (cooling transformer)

[note 2]

W1

Heat Relay Stage 1

W2

Heat Relay Stage 2

Y1

Compressor Relay Stage 1

Y2

Compressor Relay Stage 2

[note 4]

G

Fan Relay

C

24 Volt AC Transformer Common

[note 1, 3]

Heat Only or Millivolt

Set Installer Switch to CONV

Rh Power Connection

W Heat Relay (appears as W1/E on 2220)

G Fan Relay [note 4]

C 24 Volt AC Transformer Common [note 1]