Conventional systems, Heat pump systems – Braeburn 1200NC User Manual
Page 5
 
4
NOTES - Conventional Systems
[1]	If	batteries	are	installed	the	24	Volt	AC	common	connection	is	optional
[2]	Remove	factory	installed	jumper	for	dual	transformer	systems
[3]	In	dual	transformer	systems,	transformer	common	must	come	from		
	
cooling transformer
[4] If needed for system
Provide disconnect and overload protection as required.
2 HEAT / 1 COOL Single Transformer (1200NC Only)
Set System Type to NORM
 R 24	Volt	AC	Power
 W1	 Heat	Relay	Stage	1
 W2	 Heat	Relay	Stage	2
 Y1	 Compressor	Relay	Stage	1
 G	 Fan	Relay
 C	 24	Volt	AC	Transformer	Common	[note 1]
Conventional Systems
(cont.)
Typical Wiring Configurations
NOTE: The “Installer Switch” option will be configured in the next step.
Heat Pump Systems
1 HEAT / 1 COOL - No Auxiliary Heat
Set Installer Switch to HP
Rh*
24 Volt AC Power
Rc*
Connected to Rh with supplied Jumper Wire
O or B		 Changeover	Valve [note 2]
Y1 
Compressor Relay (appears as
Y1 on 1200NC)
G
Fan Relay
C
24 Volt AC Transformer Common
[note 1]
2 HEAT / 1 COOL - Including Auxiliary Heat (1200NC only)
Set Installer Switch to HP
R
24 Volt AC Power
O or B		 Changeover	Valve	[note 2]
Y1 
Compressor Relay (1st stage heating/cooling)
W2
Auxiliary Heat Relay (2nd stage heating)
[note 3]
W1/E Emergency	Heat	Relay [note 3]
G 
Fan Relay
C
24 Volt AC Transformer Common
[note1]
(Continued)
*Appears as R on 1200NC (single transformer)