VRLA

VRLA RB BATTERY RACKS
ASSEMBLY INSTRUCTIONS

(READ ALL INSTRUCTIONS PRIOR TO INSTALLATION)

Safety

Installation of VRLA batteries should only be performed and supervised by trained personnel knowledgeable of lead
acid batteries and the required personal and equipment safety precautions. Keep unauthorized personnel away from
the batteries and assembly activity.

Observe battery safety procedures. Use insulated tools, gloves, safety glasses, and remove all jewelry etc..
Special care should always be taken to avoid short circuiting any battery connection.
Wash hands after any contact with lead or electrolyte.

Rack Configurations

Racks are available in single or multiple tiers. Rack components must be assembled and secured on-site in
accordance with these C&D assembly instructions, rack drawings and applicable codes. Because EQ Racks meet
Seismic requirements, they may NOT be mechanically secured together.

A minimum distance of 3” must be allowed between racks and between racks and the building structure.














End View

Front View

K

For All Standard And Seismic Models Including Retrofitting
Standard Models To Meet Seismic Requirements

Wide Rack

Width 44.0"

Narrow Rack

Width 38.0"

1 Tier

2 Tier

3 Tier

Depth

18.5"

Depth

18.5"

Depth

18.5"

Depth

18.5"

Rack Height

55.38"

Rack Height

72.5"

4 Tier

(w/Cover)

Rack Height

21.25"

Rack Height

38.25"