10

ELECTRICAL CONNECTION

Power supply

The boiler operates with a 230 V - 50 Hz single phase supply.
A double pole isolator with a 6 amp fuse or a 6 amp MCB must be
fitted outside the boiler to allow power to be shut off during servicing
and before any repairs are carried out on the boiler.

Conformity

Boiler installation must comply with the prevailing local standards
and legislation.

Safety

The stainless steel tank must be earthed separately.

The power to the boiler must be switched off before
any work is carried out.

Alarm - module

• Connect the flat ribbon cable from the alarm-module “X7” to MCBA
connector “X8”.

The volt free relays mounted on the alarm module will now be
actived as described below:

1 - Alarm:
This contact closes if the MCBA is in lock out.

2 - External gas valve / burner - run indication:
This contact closes if a heat request is present and the fan is running.

3 - Domestic Hot Water pump:
This contact closes if a Domestic Hot water heat request is present.

• Technical data:
-

Ambient temperature:

0…60 °C

-

Contact ratings:

I

RMS

1A

230 V (+10% / 15%) 50 Hz

If inductive loads are connected, take precautions over
these loads against peak voltages (e.g. RC-network).

INSTALLATION

Connection
for transformer

1

2

3

Alarm - module

Internal MCBA connections

MCBA

X8:

Ribbon cable

connection for

alarm module

(option)

X7:

Display

connection

X1

X4

X5

X3

X2

X1: Connection MCBA 230 Volt

X2: 24 Volt connector

X3: NTC - connector

X4: NTC 5 - analogue in connector

X5: Communication / NTC 4 - connector