codes

00

02

03-07

11

12

13-17

18

19

25

28

31

32

33

36

37

38

44

Error description

No flame detected

No ignition after 5 attempts

Internal error

Eprom error

Low water pressure or 24V fuse failure

Internal error

Primary temperature 1 > 110 °C

Primary temperature 2 > 110 °C

Primary temperature 1 gradient too high

No fan signal

Short circuit in temperature 1 sensor

Short circuit in temperature 2 sensor

Hot water temperature sensor

Temperature 1 sensor: circuit open

Temperature 2 sensor: circuit open

Hot water temperature sensor: circuit open

Internal error

Fault repair

- check wiring / - change electrode / - change MCBA

- check ignition electrode and its positioning

- if the problem persists after 2 resets, change the MCBA

- if the problem persists after 2 resets, change the MCBA

- top up the primary circuit

(see Using The Boiler - Heating System Pressure)

.

- call engineer to check fuse

- if the problem persists after 2 resets, change the MCBA

- check that sensor NTC1 is propely housed in its pocket

- if so, change sensor NTC1

- check that sensor NTC2 is propely housed in its pocket

- if so, change sensor NTC2

- check that the shunt pump is operating, and if so vent the boiler

- if the fan is turning:

• check the PWM connection

• if the problem persists after 2 resets, change the fan

• if the problem persists after 2 resets, change the MCBA

- if the fan is not turning:

• check the 230 Volt power to the fan

- change sensor NTC1

- change sensor NTC2

- change sensor NTC3

- check the connection of sensor NTC1 to the terminal strip

- if the problem persists, change sensor NTC1

- check the connection of sensor NTC2 to the terminal strip

- if the problem persists, change sensor NTC2

- check the connection of sensor NTC3 to the terminal strip

- if the problem persists, change sensor NTC3

- if the problem persists after 2 resets, change the MCBA

Safety shutdown

If an operating error develops, the system locks and the display
flashes: the first digit shows the sequence the burner was in when
the error occurred, the last two digits show the error code

(see table

below)

; the first digit and the next two flash alternately.

To reset the system:
• Press the “RESET” button on the MCBA display.
• If an error occurs again, call an approved heating engineer.

Table of error codes and corrective action