Basic infinet™ setup, Infinet™ thermostat crestron chv-tstatrf – Crestron electronic CHV-TSTATRF User Manual

Page 20

Advertising
background image

infiNET™ Thermostat

Crestron CHV-TSTATRF

NOTE: The power stealing function may cause problems with some types of
HVAC systems. While rare, the symptom would be a heat or cool call occurring
when the thermostat itself does not indicate a heat or cool call. If this occurs, you
should change the power setting to “24” and ensure that you have two AA batteries
installed. Be aware that this situation will shorten the expected battery life.

If you have wired the thermostat so that 24 Volts AC will always be present on the
“C” terminal (refer to “Wiring the CHV-TSTATRF to the HVAC System” which
starts on page 10), you can set the unit to run from this power supply, thus
eliminating the need for batteries (except during initial setup). The thermostat will
run on battery power if 24 VAC is not present. In addition, when the unit detects 24
VAC is present, it will no longer “sleep”, meaning that it will offer real-time
communication with the control system.

When shipped from the factory, the CHV-TSTATRF will have a steal power setting.
If you plan to power the device from a constant 24 VAC supply, you must still install
batteries in order to access Setup mode and change the power setting to “24”.

NOTE: When the unit is powered from a constant 24 VAC supply, there may be a
slight discrepancy between the ambient temperature displayed on the thermostat and
the actual room temperature. This discrepancy will also be seen when switching from
“SP” to “24”. This is normal and the discrepancy will disappear within
approximately 10 minutes.

Basic infiNET™ Setup

The MNET ID of the CHV-TSTATRF has been factory set to 01. After an infiNET
device is added to an infiNET network, its MNET ID must be changed to a value that
can be addressed by the control system program (03 to 20). The MNET IDs of
multiple CHV-TSTATRF devices on the same gateway must be unique. MNET IDs
are changed locally using the setup parameter ability of the CHV-TSTATRF (refer to
“Setup Mode Parameters/Functions” which starts on page 20). They can also be
changed from a personal computer (PC) via the Crestron Toolbox™.

When setting the MNET ID, consider the following:

• The MNET ID of each unit must match an ID code specified in the SIMPL

Windows or D3 Pro/SystemBuilder program.

• Each network device on the same gateway must have a unique MNET ID.

In Setup mode, press MODE until the infiNET ID (MNET ID) function is displayed
(id).

Use or to choose the infiNET ID (must be in the range from 03 to 20).
Press MODE to select the infiNET RF Channel (CH).

Each infiNET device communicates with its gateway on one of 16 infiNET
channels. The gateway can be set to operate in an auto channel state, in which case it
will operate on a single channel but may switch to a new channel if it detects
excessive interference. It can also be set to operate in a fixed channel state, in which
it will stay on a specified channel indefinitely.

The RF channel on the thermostat must be set to correspond with the gateway with
which it will be communicating. For example, if the desired gateway is running in
auto channel, the thermostat must be set to auto as well. If the gateway has been set
to run on a fixed channel, the thermostat should be set to that specific channel.

16

infiNET™ Thermostat: CHV-TSTATRF

Operations & Installation Guide – DOC. 6490A

Advertising