Add the total equivalent length of the elbows determined in step 3 to the to the total straight pipe length

4)

determined in Step 2. The result is the total equivalent length.

Refer to Table 5.2, 5.3, or 5.5 as appropriate for the type of Bimini Buddy being installed. Verify that the

5)

equivalent length calculated in Step 4 is less than that shown for the combination of boiler, circulator, and

indirect water heater (BB100I only) being installed. In the case of the BB100I, the pressure drop through the

indirect water heater must be considered. The indirect water heater being used must have a pressure drop less

than that shown in Table 5.3 at the DHW flow rate shown to work reliably with the BB100I. Table 5.4 shows

the pressure drop and flow information for Crown indirect water heaters. These are grouped by “class” and that

class is shown in Table 5.4.

Table 5.2: BB100H (Heat Only) Maximum Equivalent Boiler Loop Length

Boiler Model

Circulator

Flow Rate

(GPM)

Max. Boiler Temp

Rise (F)

Pipe

Size

Max Equivalent Length of

Shaded Piping in Figure 5.6

BWC070

Taco 008

6.0

21

1”

179

BWC090

Taco 0014

8.0

20

1”

121

BWC120

Taco 0014

8.0

27

1”

152

BWC120

Taco 0014

9.0

24

1”

80

BWC120

Taco 0013

12.0

18

1”

37

BWC151

Taco 0014

8.0

34

1”

92

BWC151

Taco 0014

11.0

25

1”

54

BWC151

Taco 0013

14.0

19

1”

45

Table 5.3: BB100I (IWH) Maximum Equivalent Boiler/IWH Loop Length

Boiler

Model

Circulator

CH Mode

DHW Mode

Pipe

Size

Max

Equivalent

Length of

Shaded Piping

in Figure 5.7

Flow

Rate

(GPM)

Max.

Boiler

Temp

Rise (F)

Flow

Rate

(GPM)

Max. IWH

Pressure

Drop (ft

wc)

Indirect

Water Heater

Class in

Table 5.4

Note

BWC070

Taco 008

6.25

20

6.0

1.7

A

1

1”

79

BWC090

Taco 0014

8.0

20

7.5

2.6

A

1

1”

55

BWC120

Taco 0014

8.75

26

8.0

3.0

A

1”

37

BWC151

Taco 0014

9.25

29

8.0

5.0

B

2

1”

79

Notes:

“Class A” models shown in Table 5.4 may not achieve claimed first hour rating due to inadequate boiler water flow.

1.

MS-79 will not achieve claimed first hour rating due to inadequate boiler output.

2.

Some models shown in Table 5.4 have 3/4” boiler connections. These must be increased to 1” directly at the indirect

3.

water heater connection.

Table 5.4: Crown Indirect Water Heaters

Indirect

Water

Heater

Class

Flow Rate

(GPM)

Max. IWH

Pressure

Drop (ft wc)

Crown Indirect Water Heater Models

A

6.0

7.5

8.0

1.7

2.6

3.0

MS-26, MS-40, MSH-40, MT040GBR, MT050GBR, MT050GBR,

MT065GBR, MT080GBR

B

8.0

5.0

MS-40, MS-53, MS-79, MSH-53