Gw4500, Pre-operation (continued), Generator operation – Campbell Hausfeld Welder / Generator GW4500 User Manual

Page 7

Advertising
background image

7

www.chpower.com

GW4500

combination of 240 volt loads and
also with 120 volt loads through
the 120 volt receptacles.

The

120/240 volt twist lock

receptacle, found on some welder /
generators, is rated for 20 amps and
may be used in any combination of
120 volt and 240 volt loads.

4. Individual receptacles should not

be loaded beyond the amperage
rating.

5. Total combined load through any

combination of receptacle must
not exceed the rated load limits of
the welder / generator. Refer to the
identification plate on the welder /
generators for amp and wattage
specifications.

6. Always shut off and remove loads

before starting or shutting off the
welder / generator engine.

7. When plugging multiple electrical

load devices into the welder /
generators receptacles, be sure to
connect and activate the highest
power draw item first. Allow
the welder / generator engine to
stabilize, then connect and activate
the next highest power draw
device. The smallest power draw
device should be connected to the
receptacle and activated last.

NOTE: Power draw can be calculated
by multiplying volts and amps. The
resulting number is wattage.

Never exceed the posted maximum
wattage for the welder / generator
or any individual receptacle. Refer to
owner's manuals and product tags to
determine the wattage of all electrical
load devices.

If actual watt ratings are not available,
the Power Usage Chart, see Table 1, may
be used as a general guideline.

Remember that devices which generate
heat during operation such as heaters,
incandescent light bulbs, motors and
hair dryers have a higher power draw
than devices which generate little heat
during operation such as florescent
bulbs, radios, and clocks.

Long power cords and extension cords
also draw additional power. Keep cords
at minimum possible length.

Refer to Table 2 for maximum limits for
lengths of extension cords.

8. Circuit protection is provided by a

circuit breaker. The circuit breaker
opens when the welder / generator
load exceeds its maximum capacity
or a short circuit occurs. If the
circuit breaker opens, perform the
following procedures to correct the
problem:

a. Shut off and disconnect all

electrical loads.

b. Attempt to determine the cause

of the electrical problem -
overloading or short circuit.

c. Do not use any devices that have

short circuits. Avoid overloading
the welder / generator.

d. Press the circuit breaker

pushbutton to reset the circuit
breaker.

Repeated cycling of

the circuit breaker

indicates a problem and may cause
damage to the welder / generators or
load devices. Do not operate the
welder / generators if repeated cycling
of the circuit breaker occurs.

Pre-Operation (Continued)

LOW OIL SHUTDOWN
A low oil shutdown switch is provided
to protect the engine and welder /
generators on most extended run
models. When engine oil level drops
too low for proper engine operation,
the low oil shutdown switch causes the
engine to shut off. If oil level is low
when attempting to start the welder /
generators engine, the low oil level
shutdown switch prevents the engine
from starting. If engine does not start,
check oil level.

NOTE: It is important to keep the
welder / generator unit on a level
surface. The oil level shutdown switch
can prevent the engine from starting
even if oil level is sufficient, when the
welder / generators unit is placed on an
uneven surface.

Generator Operation

(FRONT PANEL SWITCH MUST BE SET TO
GENERATOR POSITION)

LOAD DEVICES
1. All load devices and extension cords

should use three prong terminals.
Refer to Table 2 for extension cord
and cable size requirements.

2. Allow the engine to run for 2-

3 minutes before applying any
electrical loads.

3. The

120 volt receptacles are rated

for 20 amps and may be used in any
combination of 120 volt loads and
also with 240 volt loads through
the 240 volt receptacles.

The

240 volt receptacles, found on

some welder / generators, are rated
for 20 amps and may be used in any

TABLE 1 - ESTIMATED POWER USAGE (WATTS)

LOAD DEVICE

WATTS

LOAD DEVICE

WATTS

LOAD DEVICE

WATTS

LOAD DEVICE

WATTS

Air conditioner

2000-3000

Electric drill
(large)

500-1000

Radio

50-200

Toaster

900-1700

Automatic
washer

150-1500

Fan

40-200

Refrigerator

190-2000

Vacuum cleaner

200-300

Brooder

100+

Freezer

300-500

Skillet

1200

Water pump

1000-3000

Clothes dryer

5000-10,000

Hot plate

330-1100

Space heater

600-4800

Water heater

1000-5000

Coffee maker

400-700

Iron

500-1500

Sump pump

400-3000

Small hand saw

1000-2000

Electric drill
(small)

225-1000

Light bulb

AS RATED

Television

200-500

Large hand saw

1500-2500

Advertising