Generator operation (continued), Welder operation – Campbell Hausfeld Welder / Generator GW4500 User Manual

Page 8

Advertising
background image

8

www.chpower.com

Operating Instructions and Parts Manual

Generator Operation
(Continued)

INSTALLATION FOR STAND-BY USE
Precautions must be taken to prevent
electrical back feeding into utility
systems. This requires isolation of
the electrical system. To isolate the
electrical system, perform the following
procedures:

1. Turn off the main electrical system

switch prior to connecting the
welder / generators.

2. In accordance with national and

local standards, a double throw
transfer switch must be installed in
the system.

Always shut off

main power prior to

temporary connection of the welder /
generators to a building electrical
system.

Installation of the

welder / generator

as a backup electrical source must be
performed by a qualified (licensed or
certified) electrical technician.

Welder Operation

(FRONT PANEL SWITCH MUST BE SET TO
WELDER POSITION)

WELDING LEAD ASSEMBLIES
Welding leads assemblies are not
included with all units. Use copper
welding cables in the size specified in
Table 3.

GROUND CLAMP (SEE FIGURE 1)
1. Strip 1/2 inch of insulation from the

end of one of the welding cables.

2. Loosen hex nuts on work clamp.

3. Insert the end of the welding cable

through clamp handle and slide the
bare wire under the clamp block.

4. Tighten the hex nuts, securing the

cable in place.

ELECTRODE HOLDER (SEE FIGURE 2)
1. Strip 1/2 inch of insulation from the

end of the other welding cable.
Slide the bare wire into the wire
sleeve.

2. Loosen the phillips head screw

a few turns. Do not remove it
completely.
Pull the insulated
handle off of the electrode holder,
and slide it over the welding cable.

3. Loosen the set screw on the bottom

of the electrode holder.

4. Insert the welding cable / wire

sleeve into the back of the brass
body of the electrode holder.

Figure 1

Electrode Holder

Handle Phillips Head Screw

Handle

Cable Setscrew

Wire
Sleeve

Welding
Cable

Figure 2

TABLE 3 - WELDING CABLES

Total Cable Length *

0 - 20 feet (0 - 6 m)

20 - 40 feet (6 - 12 m)

40 - 60 feet (12 - 18 m)

Maximum Welding Current

Recommended Sizes of Copper Welding Cables

100 A

6 AWG (15 mm

2

)

6 AWG (15 mm

2

)

4 AWG (20 mm

2

)

150 A

6 AWG (15 mm

2

)

3 AWG (25 mm

2

)

2 AWG (35 mm

2

)

200 A

4 AWG (20 mm

2

)

2 AWG (35 mm

2

)

1 AWG (40 mm

2

)

250 A

3 AWG (25 mm

2

)

2 AWG (35 mm

2

)

1/0 AWG (55 mm

2

)

* Total cable length is the sum of the ground and electrode cable lengths.

TABLE 2 - EXTENSION CORDS

Maximum Recommended Lengths (in feet)

Amps

Watts 120 V

Watts 240 V

#8 Wire

#10 Wire

#12 Wire

#14 Wire

#16 Wire

2.5

300

600

1000

600

375

250

5

600

1200

500

300

200

125

7.5

900

1800

350

200

125

100

10

1200

2400

250

150

100

50

15

1800

3600

150

100

65

20

2400

4800

175 125

75

50

25

3000

6000

150

100

60

30

3600

7200

125

65

40

4800

9600

90

Advertising