Crown Boiler AWI037 User Manual

Page 35

Advertising
background image

35

33

Does

spark stop

when pilot

lights?

24 volts

across

terminals 2&3

at S8600?

Spark

across

ignitor/sensor

gap?

Y

Can you

hear

sparking?

*Faulty
S8600
module

*Break in
spark cable
insulation

*Break in pilot
porcelain

*Incorrect pilot
spark gap

*Loose
connection in
spark cable

*Loose
ground
connection

N

Pilot

lights?

Y

N

N

*Defective
S8600 module

24 volts

across PV &

MV/PV at gas

valve?

*Defective EI
wiring
harness.

N

*Loose connection in
ignition cable or
ground wire

*Pilot electrode
porcelain cracked

*Pilot flame not
covering gap
between electrode
and grounding
strap

*Low gas pressure
at gas valve inlet

*Defective S8600
module

Main

burner

lights?

N

Y

24VAC

across

terminals 1&2

on S8600?

Y

N

N

*Defective
S8600
module

24 volts

between MV &

MV/PV on gas

valve?

*Defective
gas valve

*Defective EI
harness

END

START

(24 volts is present across 5 and 6 on S8600

module, but main burners do not light)

N

Y

Y

N

Y

Y

Y

* Low line pressure

*Plugged, kinked or leaking
pilot tubing

*Plugged pilot orifice

*Gas line not purged of air

*Defective pilot assembly

*Defective gas valve

Intermittent Ignition System Troubleshooting Chart

Caution: Read page 29 before

attempting to use this chart