Operating instructions – ebm-papst S3G300-AN02-52 User Manual

Page 5

Advertising
background image

Operating instructions

S3G300-AN02-52

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G074-CF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 240

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

2020

Power input / W

170

Current draw / A

1.35

Max. back pressure / Pa

140

Min. ambient temperature
/ °C

-25

Max. ambient
temperature
/ °C

60

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

43.1

24.6

28.6

Efficiency grade N

54.5

36

40

Power input P

ed

/ kW

0.16

Air flow q

v

/ m³/h

1795

Pressure increase total p

sf

/ Pa

128

Speed n / min

-1

2060

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Size

300 mm

Material of terminal box

ABS plastic, black

Material of impeller

PP plastic

Material of guard grille

Steel, coated in black plastic (RAL9005)

Number of blades

5

Direction of air flow

"V"

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"B"

Humidity class

F3-1

Mounting position

Any

Condensate discharge
holes

None, open rotor

Cooling bore / aperture

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 1.1 mA
- Tach output
- Motor current limit
- Soft start
- Control input 0-10 VDC / PWM
- Over-temperature protected
electronics / motor

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

PTC resistor

Cable exit

Variable

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

CE

Approval

CCC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

; Secure the mounting screws against accidentally coming loose (e.g.

by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

; Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

Item no. 51539-5-9970 · ENG · Revision 84194 · Release 2015-01-09 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com